button
description
Increase
1
temperature
Decrease
2
temperature
3
Set/Menu
4
ON/OFF Reset
5
Decrease power
6
Increase power
The Figure opposite describes the meaning of the status
indicators in the left part of the display.
Activation of one of the segments on the display signals
activation of the corresponding device according to the
list opposite.
4.3 Lighting
4.3.1 Check before lighting
Before lighting the boiler:
- make sure to have read and understood the information given in the manual;
- the hopper must be filled with pellets;
- the combustion chamber must be clean;
- the brazier must be completely free, cleaned of any combustion residuals and correctly fitted in the brazier
holder;
- check hermetic closing of the ash box and fire door;
- check the connection of the power cable and switching to ON/1 of the switch located on the back of the boiler.
- check opening of the delivery and return shutoff valves as well as the water circuit pressure.
- At first startup, remove all the components that could burn (instructions/label) from the boiler firebox.
- Any lighting done after long idle periods requires the removal of any residual pellets that have remained
inside the hopper, in being damp fuel no longer suitable for combustion, and complete cleaning of the
combustion chamber.
All manuals and user guides at all-guides.com
mode
Increase the WATER AND AMBIENT
SET TEMPERATURE
thermostat temperature value
PROGRAMMING
Increase the selected parameter
WORK
Display temperatures
Decrease the water and ambient thermostat
SET TEMPERATURE
temperature value
PROGRAMMING
Decrease the selected parameter
WORK
Display stove operation status
Access the SET temperature and the user
-
and technician parameters menu with
successive pressing
Press for 2 seconds to turn the stove on or
WORK
off, if off or on respectively.
BLOCK
Reset the stove, returning it to off status
Use to exit the programming menu at any
PROGRAMMING
stage of the modification. Modifications are
saved.
Decrease the power or the DHW storage
WORK/OFF
tank water thermostat Temperature value (if
enabled)
Increase the power or the DHW storage
WORK/OFF
tank water thermostat Temperature value (if
enabled)
action
External contact
Chrono
Heater
Auger
Fume extractor
DHW circuit activation
HEATING circuit activation
ALARM
52
top display
bottom display
SET H2O/air
Temperature
Selected
Parameter value
parameter
Fume temperature
Water temperature
SET H2O/air
Temperature
Selected
Parameter value
parameter
Pressure in water
fume fan speed
circuit
SET/parameter
Temperature/value
Display current
status
OFF
SET DHW
Power level
temperature
SET DHW
Power level
temperature
DOMUSFIRE C17-C24
limits
air 7°C ÷ 40
°C water
30°C ÷ 80
°C
-
-
air 7°C ÷ 40
°C water
30°C ÷ 80
°C
1-5
1-5

Werbung