3. Electrical connection

The unit must only be connected by an electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
The device shall be supplied from an isolating transformer hav-
ing a secondary Listed fuse rated as noted in the following table.
Control-circuit wire size
AWG
26
24
22
20
18
16
Disconnect power before connecting the unit.
Wiring:
1 BN
2
3 BU
When the supply voltage is applied, all LEDs light and go off one after
the other.* The unit is then ready for operation.
*During this time the output signal is 20 mA.
All manuals and user guides at all-guides.com
Overcurrent protection
2
(mm
)
(0.13)
(0.20)
(0.32)
(0.52)
(0.82)
(1.3 )
L +
/
BK
4
L
Maximum protective device rating
Ampere
1
2
3
5
7
10
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),
3 = BU (blue), 4 = BK (black).
Max. load for the analog output:
500 Ω