Herunterladen Inhalt Inhalt Diese Seite drucken

Kaco blueplanet 50.0 TL3 Kurzanleitung Seite 7

Vorschau ausblenden Andere Handbücher für blueplanet 50.0 TL3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 13
TN-S-System, TN-C-S-System, TT-System
↻ A connection cable with 5 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [
2 Remove the outer cladding of the AC cables.
3 Push an M8 cable lug onto the PE line.
4 Remove the cover of the AC filter using the 4 screws[
5 Unscrew the screws on the contact bridge and remove the contact bridge[
_T20].
6 Insert the AC cables through the cable fitting into the connection area.
7 Strip the AC lines [approx. 25 mm].
» Make the grid connection.
1
3
Fig. 4: Connection terminals - basic
version
Key
1
AC connection terminal
2
Base AC overvoltage protection
3
DC isolator switch
TN-C system
↻ Connection cable with 4 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25mm].
» Make the grid connection.
4.3.2 Make the grid connection
5 core connection for TN-S system, TN-C-S system, TT-System
↻ Grid connection is prepared.
1 Loosen nut and lock washer at the marked grounding point.
2 Lay the grounding cable onto the grounding point. Secure using the corresponding nut and lock washer [
10 Nm].
3 Connect wires in accordance with the labels on the screw terminal [
4 Check secure fit of all connected cables.
5 Tighten the cable fittings [
6 Secure cover using the 4 screws [
Photovoltaic feed-in inverter KACO blueplanet 50.0 + 60.0 TL3
W_68].
2
1
4
Fig. 5: Connection terminals - M ver-
sion
W_68].
W_68 /
20 Nm].
_T15 /
2.3 Nm].
1
4
T_15].
Fig. 3: 5-core connection
1
2
3
4
1
3
PV-
PV+
4
Fig. 6: Connection terminals S version
4
DC connection with protection against contact
5
Base DC overvoltage protection
AC side
Fig. 7: Terminals
T_45 /
10 Nm].
2
3
Cover
Screws for contact bridge
Contact bridge
Earthing bolt
4
PV+
PV-
DC-side
W_13/
Page 7