• When several LI5 units are mounted in one tank minimum
distances between them must be maintained. These depend on the
medium and the respective application.
Approximate values for common media:
Water / coolant emulsions in a grounded metal tank
Oils in a grounded metal tank
Water, hydrous media and oils in a small plastic tank
(ungrounded)
*Distance from the centreline of a probe to the centreline of ano-
ther probe. The approximate values refer to standard operating
conditions. Depending on the application greater distances can be
required. Check this by means of a realistic function test (→
"5. Installation and set-up / operation").
• Distance between sensors type LI5xxx and LKxxxx: min. 60 mm from
the centreline of a probe to the centreline of another probe.

3. Electrical connection

The unit must only be connected by an electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Disconnect power before connecting the unit,
(
= N.O. /
1
BN
4
BK
3
BU
Core colours of ifm sockets:
1 = BN (brown), 3 = BU (blue), 4 = BK (black).
14
All manuals and user guides at all-guides.com
= N.C.):
L +
L
3
BU
L +
4
BK
1
BN
L
Distance*
40 mm
100 mm
200 mm