Electrical connection

Disconnect power before connecting the proximity switch.
Connection strictly to the indications on the type label.
Core colours: BN = brown, BU = blue, BK = black.
Adjustment
The unit detects the "damped" state (= medium present) and the
"undamped" state (= no medium present) and sets the optimum
switch point.
1
Press for 5s.
2
Place the medium into the
detection area of the sensor
and press the button briefly.
3
Remove the medium and
increase the distance between
the medium and the unit until
the red LED goes out.
If the red LED does not go out, the interval between the "damped" and
Press the setting button twice. The unit passes into the operating mode
4
Press briefly.
Steps 2 and 3 can also be taken in reverse order: first align the unit without
the medium being present and then place the medium into the detection area
until the red LED goes out.
6
the "undamped" signals is too short.
with the switch point being unchanged..
Yellow and green LEDs
flash alternately
(= unit is in the
programming mode).
The yellow and green
LED's go out for a short
time, then quickly flash
alternately;
the red LED is on.
The yellow and green
LED's continue to flash
alternately.
The red LED goes out.
The yellow and green
LED's go out for a short
time, then the green LED
is on (= unit is in the
operating mode).