Outputcalibrationprocedure
All manuals and user guides at all-guides.com
Whenthe
Action/Description
displayshows
Put the instrument in setup mode and scroll through the main menu
COPn
Press
Calibrate Outputs?
COPy
Measure the output current
The output current should be 0.00 mA
I=0
(Use the keypad to adjust the value as required)
The output current should be 20.00 mA
I=20
Measure the output voltage
The output voltage should be 0.00 V
E=0
The output voltage should be 10.00 V
E=10
Instrument will save values and return to normal operation (using the new values).
Save
Note: Do not remove the power while the save message is on display.