Inputcalibrationprocedure
All manuals and user guides at all-guides.com
Whenthe
Action/Description
displayshows
Put the instrument in setup mode and scroll through the main menu
CIPn
Press
Calibrate inputs?
CIPy
Connect the current source to the inputs (for connections see over page).
Set the current source to 0.00 mA
I=0
Set the current source to 5.00 mA
I=5
Set the current source to 10.00 mA
I=10
Set the current source to 20.00 mA
I=20
Set the current source to 50.00 mA
I=50
After the display stops flashing connect the voltage source (for connections see over page).
Set the Voltage source to 0.00 V
E=0
Set the Voltage source to 5.00 V
E=5
Set the Voltage source to 10.00 V
E=10
Set the Voltage source to 20.00 V
E=20
Set the Voltage source to 50.00 V
E=50
Continue with the setup sequence.
FnC=
Note: To discard changes to calibration and setup you can remove the power at this point.
TerminalConnectionsforoutputcalibration
CalibrationStage
Analogue Current Output
Analogue Voltage Output
Å
ì
or
Signaltype
mA output +
mA output −
V output +
V output −
ENT
Start
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Calibrate
Terminal
14
15
14
16
ï
No
Skip
Skip
Skip
Skip
Skip
Skip
Skip
Skip
Skip
Skip
21