5 Installation
5.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING
5.3.1
Guidelines when connecting the
refrigerant piping
Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tightening firmly.
▪ ALWAYS use 2 wrenches together when loosening a flare nut.
▪ ALWAYS use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
a
b
c
d
a
Torque wrench
b
Spanner
c
Piping union
d
Flare nut
Piping size
Tightening
(mm)
torque (N•m)
Ø6.4
15~17
Ø9.5
33~39
Ø12.7
50~60
5.3.2
To connect the refrigerant piping to the
indoor unit
▪ Pipe length. Keep refrigerant piping as short as possible.
1 Connect refrigerant piping to the unit using flare connections.
2 Insulate the refrigerant piping, interconnection cable and drain
hose on the indoor unit as follows:
c
d
a
e
b
f
g
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
g
Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed
piping might cause condensation.
Installation manual
8
Flare
Flare shape
dimensions (A)
(mm)
(mm)
90°
±2
8.7~9.1
ØA
12.8~13.2
16.2~16.6
R=
0.4~0.8
5.4

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
5.4.1
To connect the electrical wiring to the
indoor unit
Electrical work should be carried out in accordance with the
installation manual and the national electrical wiring rules or code of
practice.
1 Set the indoor unit on the mounting plate hooks. Use the " "
marks as a guide.
a
b
c
a
Mounting plate (accessory)
b
Interconnection cable
c
Wire guide
2 Open the front panel, and then the service cover. Refer to the
Installer reference guide for opening procedure.
3 Pass the interconnection cable from the outdoor unit through
the feed-through wall hole, through the back of the indoor unit
and through the front side.
Note: In case the interconnection cable was stripped in advance,
cover the ends with insulating tape.
4 Bend the end of the cable up.
NOTICE
▪ Be sure to keep the power line and transmission line
apart from each other. Transmission wiring and power
supply wiring may cross, but may NOT run parallel.
▪ In order to avoid any electrical interference the distance
between both wirings should ALWAYS be at least
50 mm.
ATXF25~35A5V1B
Daikin room air conditioner
3P519299-6D – 2019.02