BURNER SETTINGS

5.1 COMBUSTION HEAD SETTING

Factory calibration is set for medium power;
according to the boiler output:
Loosen screw (A) and shift the elbow (B) such
that the rear surface of the head assembly cast-
ing (C) coincides with the desired notch. Tight-
en screw (A).
C
A
B
Example:
The burner type 729 T50 is installed in a 77 kW
boiler.
The burner will have to deliver about 85 kW, con-
sidering an efficiency of 90%.
The diagram indicates, that for this output the el-
bow (B) is adjusted to set-point 4.
NOTE
The diagram is indicative only.
The head setting may require adjustment to
suit the boiler characteristics.
A
Ignition electrode
A
B
40 mm
2.2
47 mm
3.7
S7015
Diffuser
B
WARNING 2 – 3 mm