Herunterladen Diese Seite drucken

Belden Hirschmann OCTOPUS HiOS-2A Referenzhandbuch Seite 927

Vorschau ausblenden Andere Handbücher für Hirschmann OCTOPUS HiOS-2A:

Werbung

Industrieprotokolle
16.3 EtherNet/IP
Tab. 61:
Id
Attribute
0x1 Switch Status
382
Class-Attribute
Access
Rule
Get
Data type
DWORD
Description
0:
Like the signal contact, the
value indicates the Device
Overall state
(0=ok, 1=failed)
1:
Device Security Status
(0=ok, 1=failed)
2:
Power Supply 1
(0=ok, 1=failed)
3:
Power Supply 2
(0=ok, 1=failed or not existing)
4:
Reserved
5:
Reserved
6:
Signal Contact 1
(0=closed, 1=open)
7:
Signal Contact 2
(0=closed, 1=open or not
existing)
8:
Reserved
9:
Temperature
(0=ok, 1=failure)
10:
Module removed (1=removed)
11:
ACA21/ACA22 removed
(1=removed)
12:
ACA31 removed (1=removed)
13:
Reserved
14:
Reserved
15:
Reserved
16:
Reserved
17:
Reserved
18:
Reserved
19:
Reserved
20:
Reserved
21:
Reserved
22:
Reserved
23:
MRP (0=disabled, 1=enabled)
24:
PRP (0=disabled, 1=enabled)
25:
HSR (0=disabled, 1=enabled)
26:
RSTP (0=disabled, 1=enabled)
27:
LAG (0=disabled, 1=enabled)
28:
DLR (0=disabled, 1=enabled)
29:
Reserved
30:
Reserved
31:
Connection Error (1=failure)
UM Config OCTOPUS
Release 8.6 12/2020

Werbung

loading