Technical specifications
Ex-AI 2xI 2-wire HART
Supply voltage
Type of supply voltage
Input current
Current consumption (rated value)
Current consumption, max.
Encoder supply
24 V encoder supply
24 V
Short-circuit protection
Output current per channel, max.
Power loss
Power loss, typ.
Power loss, max.
Ex(i) characteristic values
Maximum values for terminals for gas
group IIC
U
(no-load voltage), max.
o
I
(short-circuit current), max.
o
P
(output power), max.
o
C
(permissible external capacity), max. 99
o
L
(permissible external inductance),
o
max.
U
(intrinsically safe input voltage),
i
max.
U
(voltage at non-intrinsically safe
m
terminals), max.
Electrical isolation
Electrical isolation channels
Between the channels
Between the channels and the
backplane bus
Ex-AI 2xI 2-wire HART
DC supply via Ex-PM-E
74
mA
92
mA
Peak load (all channels in
short-circuit)
Yes
Yes
Electronic disconnection in short-
circuit, current limitation from 27
mA
28
mA
1.2
W
2.3
W
Peak load (all channels in
short-circuit)
26
V
93
mA
605
mW
nF
4
mH
10
V
60
V
No
Yes
Ex-AI 2xI 2-wire HART