The maintenance-free, microprocessor-controlled AERASGARD
this, the CO
concentration is measured within in the range of 0...2000 ppm or 0...5000 ppm and converted into standard signals (0 -10 V or
2
4...20 mA). Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment, for installation on vertically or horizontally installed
in-wall flush boxes, with predetermined breaking point for on-wall cable entry. The CO
(non-dispersive infra-red technology).

TECHNICAL DATA

Voltage supply:
Power consumption:
Sensor CO
:
2
Measuring range, CO
:
2
Output CO
:
2
Measuring accuracy CO
:
2
Temperature dependence CO
Pressure dependence:
Long-term stability:
Gas exchange:
Relay output:
Ambient temperature:
Warm up time:
Response time:
Electrical connection:
Enclosure:
Dimensions:
Installation:
Protection class:
Protection type:
Standards:
®
AERASGARD
RCO
- W
2
Type ⁄ WG02
RCO
- W
2
R C O 2 -W
R C O 2 -W- A
Note:
- W ⁄ RCO
- W-A
2
2
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; peak current 200 mA
optical NDIR sensor (non-dispersive infra-red technology)
with automatic and manual calibration
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
0 -10 V or 4...20 mA (selectable via DIP switches)
± 30 ppm ± 3 % of measured value
:
± 5 ppm ⁄ °C or
2
± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
with potential-free changeover contact 24 V (assignment selectable via DIP switches)
0...+ 50 °C
approx. 1 hour
< 2 minutes
2
0.14 - 1.5 mm
, via screw terminals
plastic, material ABS, colour pure white (similar to RAL 9010)
85 x 85 x 27 mm (Baldur 1)
wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes, for attachment to
vertically or horizontally installed in-wall flush boxes for rear cable entry, with predetermined
breaking point for cable entry from top ⁄ bottom in case of plain on-wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive 2014 ⁄ 35 ⁄ EU
Room CO
sensors and measuring transducers, Deluxe
2
Measuring Range
Humidity
Temperature
This unit must not be used as safety-relevant device!
®
RCO
- W or RCO
- W - A is used to monitor the entire room climate. In order to do
2
2
content of the air is measured using an optical NDIR sensor
2
CO
VOC
2
(switchable)
0...2000 ⁄ 5000 ppm
0...2000 ⁄ 5000 ppm
*
Equipment and enclosure:
W = 1x changeover contact
A = "traffic light" (5x LED)
B1 = enclosure Baldur 1
*
Item No.
Display
W, B1
1501-61A0-7301-200
WA, B1
1501-61A0-7331-200
Rev. 2017 - V25 GB