Herunterladen Inhalt Inhalt Diese Seite drucken
S+S REGELTECHNIK AERASGARD RCO2-W Bedienungs- Und Montageanleitung

S+S REGELTECHNIK AERASGARD RCO2-W Bedienungs- Und Montageanleitung

Multifunktionaler raumfühler
Vorschau ausblenden Andere Handbücher für AERASGARD RCO2-W:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

  • DEUTSCH, seite 3
D G F r
6003-3200-2016-000 33200-2017 V102 02 ⁄ 2017
RCO
AERASGARD
® 
RFTM - LQ - CO
AERASGARD
® 
D
Bedienungs- und Montageanleitung
Multifunktionaler Raumfühler bzw.
Messumformer für Feuchte, Temperatur,
Luftgüte (VOC) und CO
- Gehalt,
2
kalibrierfähig, mit aktivem ⁄ schaltendem Ausgang
G
Operating Instructions, Mounting & Installation
Multifunctional room sensors and
measuring transducers, for humidity, temperature,
air quality (VOC) and CO
2
calibratable, with active ⁄ switching output
F
Notice d'instruction
Sonde d'ambiance (transmetteur) multifonctionnelle,
pour l'humidité, la température,
la qualité d'air (COV) et de teneur en CO
étalonnable, avec sortie active ⁄ tout ou rien
r
Руководство по монтажу и обслуживанию
Мультифункциональный датчик для
помещений ⁄ измерительный преобразователь,
для измерения влажности, температуры,
качества воздуха (VOC) и содержания CO
калибруемый, с активным ⁄ релейным выходом
S+S REGELTECHNIK GMBH
PIRNAER STRASSE 20
90411 NÜRNBERG ⁄ GERMANY
FON +49 (0) 911 ⁄ 5 19 47- 0
FAX +49 (0) 911 ⁄ 5 19 47- 70
mail@SplusS.de
www.SplusS.de
- W ⁄ RLQ - CO
2
2
content,
,
2
,
2
- W
2
Herzlichen Glückwunsch!
Sie haben ein deutsches Qualitätsprodukt erworben.
Congratulations!
You have bought a German quality product.
Félicitations !
Vous avez fait l'acquisition d'un produit allemand de qualité.
Примите наши поздравления !
Вы приобрели качественный продукт, изготовленный в Германии.
(Baldur 2 )

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für S+S REGELTECHNIK AERASGARD RCO2-W

  • Seite 1 Мультифункциональный датчик для помещений ⁄ измерительный преобразователь, для измерения влажности, температуры, качества воздуха (VOC) и содержания CO калибруемый, с активным ⁄ релейным выходом S+S REGELTECHNIK GMBH Herzlichen Glückwunsch! Sie haben ein deutsches Qualitätsprodukt erworben. PIRNAER STRASSE 20 Congratulations! 90411 NÜRNBERG ⁄ GERMANY You have bought a German quality product.
  • Seite 2 D G F r - W ⁄ RLQ - CO AERASGARD ®  RFTM - LQ - CO AERASGARD ®  Maßzeichnung Gehäuse Baldur 2 Dimensional drawing Enclosure Baldur 2 Plan coté boîtier Baldur 2 Габаритный чертеж Корпус Baldur 2 32.6...
  • Seite 3: Technische Daten

    ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 DE Der wartungsfreie mikroprozessorgesteuerte AERASGARD ® RFTM - LQ - CO bzw. RCO - W ⁄ RLQ - CO - W dient zur Erfassung des gesamten Raum- klimas.
  • Seite 4 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 DE Feuchtetabelle Temperaturtabelle MB: 0...100 % r. H. MB: 0...+50 °C °C r.H. in V in mA r.H. in V in mA in V in mA...
  • Seite 5 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 DE Schaltbild RFTM - LQ - CO (Baldur 2) Sensor Stecker Display 1 2 3 CO ² MODE Ausgänge Luftgüte (VOC) Temperatur in °C 1 2 3 1 2 3...
  • Seite 6: Montage Und Installation

    Montage und Installation ACHTUNG !  Die minimale CO - Konzentration von Außenluft beträgt in begrünten, industrie armen Gegenden ca. 350 ppm (Ausgangs spannung = 1,75 V bei MB = 2000 ppm bzw. 0,7 V bei MB = 5000 ppm). Der Gas austausch im Sensorelement erfolgt durch Diffusion. Je nach Konzentrationsänderung und Strömungs geschwindigkeit der Luft in Sensor umgebung kann die Reaktion des Gerätes auf die Konzentrationsänderung verzögert auftreten.
  • Seite 7 Montage und Installation Inbetriebnahme Nach dem Einschalten des Gerätes erfolgen ein Selbsttest und die Temperierung. Dieser Vorgang dauert je nach Umgebungsbedingun gen 30 - 50 Minuten, in dieser Zeit weicht die ausgegebene Analog spannung vom tatsächlichen Messwert ab. Schaltpunkteinstellung Über das Potentiometer SET kann ein Schaltpunkt zwischen 10 % und 95 % des des Messbereichs gewählt werden. Der 10 % - Wert wird bei CO Frischluftgrenze von 400 ppm addiert.
  • Seite 8 Montage und Installation VERSORGUNGSSPANNUNG: Schaltbild Einzelbetrieb Als Verpolungsschutz der Betriebsspannung ist bei dieser Gerätevariante eine Einweggleichrichtung bzw. Verpolungschutzdiode integriert. Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC-Versorgungs- spannung. Das Ausgangssignal ist mit einem Messgerät abzugreifen. Hierbei wird Schaltung die Ausgangssignal gegen das Nullpotenial (O V) der Eingangsspannung Versorgung mit ge messen! AC 24V~...
  • Seite 9: Wichtige Hinweise

    Wichtige Hinweise – Dieses Gerät darf nur in schadstofffreier, nicht kondensierender Luft, ohne Über- oder Unterdruck am Sensorelement eingesetzt werden. – Bei Aussen- und Kanalfühlern schützt der Sinterfilter des Sensorelementes den Feuchtesensor vor eventuellen Staub belastungen. Dieser Filter sollte bei Verunreinigung ⁄ Verschmutzung regelmäßig gewartet werden. –...
  • Seite 10: Technical Data

    ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 GB The maintenance-free, microprocessor-controlled AERASGARD ® RFTM - LQ - CO and RCO - W ⁄ RLQ - CO - W is used to monitor the entire room climate. For this purpose, measurands air humidity, temperature, CO concentration as well as air quality (VOC) are measured.
  • Seite 11 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 GB Humidity table Temperature table MR: 0...100 % r. H. MR: 0...+50 °C °C r.H. in V in mA r.H. in V in mA in V...
  • Seite 12 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 GB Schematic diagram RFTM - LQ - CO (Baldur 2) Plug for sensor display 1 2 3 CO ² MODE Outputs air quality (VOC) temperature in °C...
  • Seite 13 Mounting and Installation ATTENTION!  The minimum CO concentration of outdoor air amounts to approx. 350 ppm (output voltage = 1.75 V at MR = 2000 ppm or 0.7 V at MR = 5000 ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with a delay.
  • Seite 14 Mounting and Installation Putting in operation After switching on the device, a self-test and tempering period follows. This procedure takes 30 - 50 minutes,depending on the ambient conditions. During this time the output analogue voltage differs from the actual measured value. Switching point setting A switching point between 10 % and 95 % of the measuring range can be selected using the SET potentiometer.
  • Seite 15 Mounting and Installation SUPPLY VOLTAGE : Connecting scheme Individual operation For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier on AC supply voltage. The output signal is to be tapped by a measuring instrument. The output signal is measured her against zero potential (O V) of the input voltage! Circuitry When this device is operated on DC supply voltage , the operating voltage...
  • Seite 16 General notes – This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. – On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure. In case of pollution ⁄...
  • Seite 17: Caractéristiques Techniques

    ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 FR La sonde AERASGARD ® RFTM - LQ - CO ou RCO - W ⁄ RLQ - CO - W commandée par microprocesseur sans entretien sert à enregistrer les données relatives au climat ambiant dans son ensemble.
  • Seite 18 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 FR Tableau d'humidité Tableau de température plage de mesure : 0...100 % r. H. plage de mesure : 0...+50 °C °C h.r.
  • Seite 19 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 FR Schéma de raccordement RFTM - LQ - CO (Baldur 2) Plug for sensor display 1 2 3 CO ² MODE Outputs air quality (VOC)
  • Seite 20: Montage Et Installation

    Montage et installation ATTENTION !  La teneur minimale en CO de l'air extérieur dans des régions vertes à faible degré d'industrialisation est de l'ordre 350 ppm (tension de sortie = 1,75 V à MB = 2000 ppm, resp. 0,7 V à MB = 5000 ppm). L'échange de gazdans l'élément capteur s'effectue par diffusion. En fonction de la variation de la concentration et de la vitesse d'écoulement de l'air dans l'environnement du capteur, la réaction de l'appareil à...
  • Seite 21 Montage et installation Mise en service Après la mise en marche de l’appareil, celui-ci effectue un autocontrôle et l’équilibrage de température. En fonction des conditions d'environnement, cette opération dure entre 30 - 50 minutes, pendant ce temps la tension analogique émise diffère de la valeur de mesure réelle. Réglage du point de commutation Un point de commutation entre 10 % et 95 % de la plage de mesure peut être sélectionné...
  • Seite 22 Montage et installation TENSION D’ALIMENTATION : Schéma de raccordement individuel Cette variante d’appareil est dotée d’une protection contre l’inversion de polarité, c’.-à.-d. elle comprend un redressement demi-onde (diode de redresse ment). Grâce à cette diode de redressement intégrée, les appareils 0 -10 V peuvent également être alimentés en courant alternatif.
  • Seite 23: Généralités

    Généralités – Cet appareil ne doit être utilisé que dans un air non pollué, sans risque de condensation, sans risque de surpression ou dépression sur l’élément sensible. – Dans le cas des sondes extérieures et des sondes pour montage en gaine, le filtre fritté de l’élément sensible protège la sonde d’humidité contre la pénétration des particules de poussières.
  • Seite 24: Технические Данные

    ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 RU Не нуждающийся в техническом обслуживании, управляемый микропроцессором датчик AERASGARD ® RFTM - LQ - CO или RCO - W ⁄ RLQ - CO служит...
  • Seite 25 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 RU Таблица значений влажности Таблица значений температуры Диап. вл.: 0 …100 % отн. вл. Диап. темп.: 0...+50 °C °C отн. вл. В...
  • Seite 26 ® AERASGARD - W ⁄ RLQ - CO - W ⁄ RFTM - LQ - CO Rev. 2017 - V25 RU Схема подключения RFTM - LQ - CO (Baldur 2) Plug for sensor display 1 2 3 CO ² MODE Outputs air quality (VOC) temperature in °C...
  • Seite 27: Монтаж И Подключение

    Монтаж и подключение ВНИМАНИЕ!  Минимальная концентрация CO в наружном воздухе в озелененных районах с малым количеством промышленных объектов составляет прибл. 350  млн (выходное напряжение = 1,75  В при диапазоне измерения 2000  млн или 0,7  В при диапазоне измерения 5000  млн ).
  • Seite 28 Монтаж и подключение Запуск в эксплуатацию После включения прибора начинается самотестирование и терморегулирование. Этот процесс длится от 30 до 50 минут в зависимости от условий окружающей среды; в это время выходное аналоговое напряжение отличается от измеренного значения. Настройка порога переключения Порог переключения настраивается между 10 % и 95 % диапазона измерения с помощью потенциометра SET. Для CO значение, соответствующее...
  • Seite 29 Монтаж и подключение НАПРЯЖЕНИЕ ПИТАНИЯ: Схема соединения Одиночное подключение В качестве защиты от неправильного подключения рабочего напряжения в данный вариант прибора интегрирован однополупериодный выпрямитель или диод защиты от напряжения обратной полярности. В случае приборов, рассчитанных на напряжение 0 – 10 В, этот встроенный выпрямитель допускает...
  • Seite 30 Указания к продуктам – Данный прибор допускается применять только в воздухе без конденсата и вредных веществ, при отсутствии пониженного или повышенного давления вблизи чувствительного элемента. – В случае датчиков для наружной и канальной установки защита чувствительного элемента датчика влажности от возможного скопления пыли обеспечивается...
  • Seite 31 Reprints, in part or in total, are only permitted with the approval of S+S Regeltechnik GmbH. La reproduction des textes même partielle est uniquement autorisée après accord de la société S+S Regeltechnik GmbH. Перепечатка, в том числе в сокращенном виде, разрешается лишь с согласия S+S Regeltechnik GmbH.
  • Seite 32 D G F r - W ⁄ RLQ - CO AERASGARD ®  RFTM - LQ - CO AERASGARD ® ...

Diese Anleitung auch für:

Aerasgard rlq-co2-wAerasgard rftm-lq-co2

Inhaltsverzeichnis