Herunterladen Diese Seite drucken

janitza UMG 103-CBM Installationsanleitung Seite 10

Vorschau ausblenden Andere Handbücher für UMG 103-CBM:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Example: PC connection via RS485 interface and UMG 604 as gateway
Example: PC connection via RS485 interface and UMG 604 as gateway
12
12
The PC connection of the device via the RS485
The PC connection of the device via the RS485
serial interface with, for example, an UMG 604
serial interface with, for example, an UMG 604
Supply voltage
Supply voltage
as gateway (see step "Established connection to
as gateway (see step "Established connection to
The device gets the supply voltage from the measuring voltage!
The device gets the supply voltage from the measuring voltage!
PC") is a method
PC") is a method
Supply from single phase
Supply from single phase
115 - 277 V (+-10%), 50/60 Hz
115 - 277 V (+-10%), 50/60 Hz
• for configuring the device(s)
• for configuring the device(s)
Supply from three phases
Supply from three phases
80 - 277 V (+-10%), 50/60 Hz
80 - 277 V (+-10%), 50/60 Hz
• and reading out data.
• and reading out data.
Power consumption
Power consumption
max. 1.5 VA
max. 1.5 VA
RS485 bus
RS485 bus
Voltage measurement
Voltage measurement
e.g. connection to the
A
A
e.g. connection to the
A
3-phase, 4-conductor
3-phase, 4-conductor
UMG 604 as gateway
UMG 604 as gateway
B
B
B
systems with rated voltages
systems with rated voltages
max. 277 V/480 V
max. 277 V/480 V
(Master)
(Master)
(L-N/L-L)
(L-N/L-L)
Measurement in TT and TN
Measurement in TT and TN
Networks
Networks
networks
networks
C
A
B
A
C
Rated surge voltage
Rated surge voltage
4 kV
4 kV
Protection of
Protection of
1 - 10 A Trip characteristic B,
1 - 10 A Trip characteristic B,
voltage measurement
voltage measurement
(With IEC / UL approval)
(With IEC / UL approval)
Overvoltage category
Overvoltage category
300 V CAT III
300 V CAT III
Resolution
Resolution
0.01 V
0.01 V
Crest factor
Crest factor
2 (related to 240 Vrms)
2 (related to 240 Vrms)
Sampling rate
Sampling rate
5.4 kHz
5.4 kHz
Frequency range of
Frequency range of
the fundamental oscillation -
the fundamental oscillation -
45 Hz .. 65 Hz
45 Hz .. 65 Hz
resolution
resolution
0.01 Hz
0.01 Hz
Fourier analysis
Fourier analysis
1.-40. Harmonic
1.-40. Harmonic
Fig. UMG 103-CBM
Fig. UMG 103-CBM
FCC Compliance Statement
FCC Compliance Statement
This equipment has been tested and found to comply with the limits for
This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These
a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used
and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to
in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference
radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be de-
harmful interference to radio or television reception, which can be de-
termined by turning the equipment off and on, the user is encouraged to
termined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
try to correct the interference by one or more of the following measures:
—Reorient or relocate the receiving antenna.
—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different from that
—Connect the equipment into an outlet on a circuit different from that
to which the receiver is connected.
to which the receiver is connected.
—Consult the dealer or an experienced radio/TV technician for help.
—Consult the dealer or an experienced radio/TV technician for help.
Code of Federal Regulations, Title 47, Part 15, Subpart B -
Code of Federal Regulations, Title 47, Part 15, Subpart B -
Unintentional Radiators
Unintentional Radiators
RS485 bus structure
RS485 bus structure
• In an RS485 bus structure (line), you connect
• In an RS485 bus structure (line), you connect
Current measurement
Current measurement
all devices in accordance with the Master-Slave
all devices in accordance with the Master-Slave
Nominal current
Nominal current
5 A
5 A
principle.
principle.
Rated current
Rated current
6 A
6 A
• One segment of an RS485 bus structure can
• One segment of an RS485 bus structure can
Crest factor
Crest factor
2 (related to 6 Arms)
2 (related to 6 Arms)
include up to 32 subscribers/devices.
include up to 32 subscribers/devices.
Resolution
Resolution
0.1 mA
0.1 mA
• Terminate the cable at the start and end of a
• Terminate the cable at the start and end of a
Measuring range
Measuring range
0.005 ... 6 Arms
0.005 ... 6 Arms
segment with termination resistors (120 Ω, 0.25 W).
segment with termination resistors (120 Ω, 0.25 W).
Overvoltage category
Overvoltage category
300 V CAT II
300 V CAT II
e.g. connection
A
e.g. connection
Rated surge voltage
The device has no termination resistor.
Rated surge voltage
The device has no termination resistor.
2 kV
2 kV
to further
to further
B
Slave devices
Slave devices
• With more than 32 subscribers, repeaters must
Power consumption
• With more than 32 subscribers, repeaters must
Power consumption
approx 0.2 VA (Ri=5 mΩ)
approx 0.2 VA (Ri=5 mΩ)
Overload for 1 sec.
Overload for 1 sec.
60 A (sinusoidal)
60 A (sinusoidal)
be used to connect segments.
be used to connect segments.
Sampling rate
Sampling rate
5.4 kHz
5.4 kHz
B
Correct
Correct
Terminal connection capacity
Terminal connection capacity
Terminal strip (switch cabinet).
Terminal strip (switch cabinet).
Conductors to be connected.
Conductors to be connected.
Device with RS485 interface
Device with RS485 interface
Only one conductor can be connected per terminal!
Only one conductor can be connected per terminal!
(without termination resistor).
(without termination resistor).
Incorrect
Incorrect
Single core, multi-core,
Single core, multi-core,
0.08 - 2.5 mm
0.08 - 2.5 mm
fine-stranded
fine-stranded
Device with RS485 interface
Device with RS485 interface
Tightening torque
Tightening torque
max. 0.5 Nm (0.74 ft lb)
max. 0.5 Nm (0.74 ft lb)
(termination resistor on the
(termination resistor on the
Stripping length
Stripping length
min. 8 mm (0.32 in)
min. 8 mm (0.32 in)
device).
device).
C C
C C
NOTE!
NOTE!
RS485 interface
RS485 interface
The coding switches can be used in the
The coding switches can be used in the
Protocol, modbus RTU
Protocol, modbus RTU
Modbus RTU/Slave
Modbus RTU/Slave
RS485 bus structure to allocate the Slave
RS485 bus structure to allocate the Slave
9.6 kbps, 19.2 kbps,
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
38.4 kbps, 57.6 kbps,
devices (UMG 103-CBM)
devices (UMG 103-CBM)
Transfer rate
Transfer rate
115.2 kbps,
115.2 kbps,
• different device addresses.
• different device addresses.
automatic detection
automatic detection
• different device addresses to the Master
• different device addresses to the Master
C C
C C
NOTE!
NOTE!
device (UMG 604).
device (UMG 604).
Further technical data can be found in
Further technical data can be found in
The UMG 103-CBM detects the transmission
The UMG 103-CBM detects the transmission
the user manual for the device.
the user manual for the device.
speed (Baud rate) automatically!
speed (Baud rate) automatically!
Connections and control elements
Connections and control elements
13
13
15
15
Procedure in the event of faults
Procedure in the event of faults
Current measurement connection
Current measurement connection
Possible fault
Possible fault
No LED lights
No LED lights
Measured current is too large
Measured current is too large
or too small. *
or too small. *
Measured voltage is too large
Measured voltage is too large
or too small. *
or too small. *
Measured voltage is too
Measured voltage is too
small. *
small. *
, AWG 28 - 12
, AWG 28 - 12
2
2
Connection of measurement
Connection of measurement
voltage and supply voltage
voltage and supply voltage
Active power is too large or
Active power is too large or
too small. *
too small. *
Coding switches
Coding switches
You can configure the device address with the
You can configure the device address with the
coding switches as follows:
coding switches as follows:
Active power imported
Active power imported
supply / supply is reversed.
supply / supply is reversed.
Configure the device addresses in
x1
x1
the range of 01 to 99 with the coding
No connection with the device. RS485: Device address is incorrect or wrong protocol.
No connection with the device. RS485: Device address is incorrect or wrong protocol.
(1-9)
(1-9)
switches.
Despite the measures above
Despite the measures above
the device does not work.
the device does not work.
The device address 00 is reserved for
x10
x10
m m
m m
service purposes (further information
*...
CAUTION!
*...
(10-90)
(10-90)
in the user manual).
10 / 10
10 / 10
(gedrehtes Patchkabel)
(gedrehtes Patchkabel)
(gedrehtes Patchkabel)
(gedrehtes Patchkabel)
LEDs
LEDs
C
A
B
C
A
B
The green LED illuminates. Measurement
RS485
RS485
Cause
Cause
Interface
Interface
and supply voltages lie within the operating
External fusing for the power supply voltage has tripped. Replace fuse.
External fusing for the power supply voltage has tripped. Replace fuse.
voltage range. The device is operational.
Device is defective.
Device is defective.
Coding
Coding
The LED flashes for 0.5 sec. every 5 secs.
Current measurement in the wrong phase.
Current measurement in the wrong phase.
switches
switches
for setting the
for setting the
The green LED flashes.
Current transformer factor programmed incorrectly.
Current transformer factor programmed incorrectly.
device address
device address
Data transfer (RS485) is active.
The peak current value at the measurement input has
The peak current value at the measurement input has
been exceeded by harmonic components.
been exceeded by harmonic components.
The LEDs flash at the same time.
Underrange.
Underrange.
The data transfer (RS485) is faulty.
Voltage measurement in the wrong phase.
Voltage measurement in the wrong phase.
Red LED
Red LED
The red LED illuminates. Fault in the device!
Voltage transformer incorrectly programmed.
Voltage transformer incorrectly programmed.
Have the device checked by the manufacturer!
Green LED
Green LED
Underrange.
Underrange.
The peak voltage value at the measurement input has
The peak voltage value at the measurement input has
The red LED flashes. At least one current
been exceeded by harmonic components.
been exceeded by harmonic components.
measurement input or voltage measurement
The programmed current transformer transformation
The programmed current transformer transformation
ratio is incorrect.
ratio is incorrect.
input exceeds the measurement range.
The current path is assigned to the wrong voltage path. Check connection and correct if necessary.
The current path is assigned to the wrong voltage path. Check connection and correct if necessary.
The programmed voltage transformer transformation
The programmed voltage transformer transformation
The LEDs flash alternately.
ratio is incorrect.
ratio is incorrect.
Firmware checksum fault! Operation is
At least one current transformer connection is mixed
At least one current transformer connection is mixed
interrupted! Carry out a firmware update!
up/reversed.
up/reversed.
Configure the device addresses in
A current path is assigned to the wrong voltage path.
A current path is assigned to the wrong voltage path.
the range of 01 to 99 with the coding
switches.
Device is defective.
Device is defective.
The device address 00 is reserved for
Material damage from overloaded measurement inputs!
Material damage from overloaded measurement inputs!
service purposes (further information
CAUTION!
Too high current and voltage values overload the measurement inputs.
Too high current and voltage values overload the measurement inputs.
in the user manual).
Observe the limits stated on the nameplate and in the user manual!
Observe the limits stated on the nameplate and in the user manual!
The green LED illuminates. Measurement
Remedy
Remedy
and supply voltages lie within the operating
voltage range. The device is operational.
Send device to the manufacturer for repair.
Send device to the manufacturer for repair.
The LED flashes for 0.5 sec. every 5 secs.
Check connection and correct if necessary.
Check connection and correct if necessary.
The green LED flashes.
Read out current transformer ratio and program.
Read out current transformer ratio and program.
Data transfer (RS485) is active.
Install current transformers with a larger current
Install current transformers with a larger current
transformer ratio.
transformer ratio.
The LEDs flash at the same time.
Install current transformers with a smaller current
Install current transformers with a smaller current
transformer ratio.
transformer ratio.
The data transfer (RS485) is faulty.
Check connection and correct if necessary.
Check connection and correct if necessary.
The red LED illuminates. Fault in the device!
Read out voltage transformer ratio and program.
Read out voltage transformer ratio and program.
Have the device checked by the manufacturer!
Install voltage transformers.
Install voltage transformers.
Attention. It must be ensured that the measuring
Attention. It must be ensured that the measuring
The red LED flashes. At least one current
inputs are not overloaded.
inputs are not overloaded.
measurement input or voltage measurement
Read out current transformer ratio and program with
Read out current transformer ratio and program with
the software GridVis.
input exceeds the measurement range.
the software GridVis.
The LEDs flash alternately.
Read out voltage transformer ratio and program.
Read out voltage transformer ratio and program.
Firmware checksum fault! Operation is
interrupted! Carry out a firmware update!
Check connection and correct, if necessary.
Check connection and correct, if necessary.
Adjust the device address / select protocol.
Adjust the device address / select protocol.
Send device and error description to verify the
Send device and error description to verify the
manufacturer.
manufacturer.

Werbung

loading