Bosch Rexroth AG | Bedienoberfläche Schweissen / Resistance welding user interface VCP05.2 | R911172348
8

PST Configuration

For application with PST6xxx please load project from CD R911171779 :
Project upload to VCP05
(USB-Stick is necassary)
First of all copy the files to an USB-Stick into path TSvisRT.
1. After Power On select Setup Main Menu with
2. Select Update . (Always confirm with
3. Select Copy USB Stick .
4. Plug USB-Stick to VCP (both on the backside are possible).
5. Select Copy to Flash .
6. With
or
and confirm with
7. Text: „Press Start to copy data" should appear. Confirm with
8. Data will be copied to the VCP flash memory..
9. The VCP will boot and the update is finished.
9

Ethernet Communication

Changing the timer IP-adresses in the
connection table of the VCP
(USB-Stick is necessary; not necessary with VCH08,
because there is only one connection possible)
1. Plug the USB-Stick into VCP, then VCP switch Off/On.
2. After booting choose Setup Main Menu with
).
select the project (dark highlighted)
.
button .