Herunterladen Inhalt Inhalt Diese Seite drucken

Troubleshooting - Dometic COOLMATIC CRP40 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für COOLMATIC CRP40:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CRP40
12

Troubleshooting

Compressor does not run
Fault
U
= 0 V
TERM
≤ U
U
TERM
ON
Start attempt with
≤ U
U
TERM
OFF
Start attempt with
≥ U
U
TERM
ON
Electric circuit between
the pins in the compres-
sor interrupted
Usage when the
ambient temperature is
too low
U
Voltage between the positive and negative terminals of the electronics
TERM
U
Cut-in voltage of the electronics
ON
U
Cut-off voltage of the electronics
OFF
EN
Possible cause
There is an interruption in the
connection between the battery and
the electronics
Main switch faulty (if installed)
Additional supply line fuse has blown
(if installed)
Battery voltage is too low
Loose cables
Poor contact (corrosion)
Battery capacity too low
Cable cross section too small
Ambient temperature too high
Insufficient ventilation and/or air
supply
Condenser is dirty
Fan defective (if installed)
Defective compressor
The compressor only starts up at an
ambient temperature of more than
+16 °C.
Troubleshooting
Remedy
Establish a connection
Replace the main switch
Replace the supply line
fuse
Charge the battery
Establish a connection
Replacing the battery
Replace the cable
(fig. 9, page 6)
Move the refrigerator to
another location
Clean the condenser
Replace the fan
Replace the compressor
Only switch on the refrig-
erator at an ambient tem-
perature of more than
+16 °C.
21

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Coolmatic crp 40s

Inhaltsverzeichnis