CAUTION!
Non- or erroneously-connected cables
Malfunctions, which endanger the safety of operating
personnel.
Work on electrical equipment may only be performed
by specialist electric technicians.
Observe regulation IEC 30364 (DIN VDE 0100) and
for explosion protection IEC 60079 (DIN VDE 0165).
CAUTION!
Faulty mains connection
Damage to the electricity network, short circuit!
Observe the conditions for technical connections of
the local power supply companies.
CAUTION!
Improperly connected wiring and lines (e.g. too
small bend radius)
Smouldering and fires from cables.
Work on electrical equipment may only be performed
by specialist electric technicians.
CAUTION!
Live cable ends and components
Make sure the protective earth system is connected
throughout.
The installation of a motor protection device is
recommended.
1.
Compare the mains voltage with the specifications on
the type label.
2.
Insert mains plug in the electrical socket.
6.8 Verification of the waterflow
The water shortage monitor must not be activated at maximal
withdrawal.
Should the water shortage monitor nevertheless be activated,
then the pressure side must be throttled. For maximum
withdrawal and inlet amounts see 3 Description.
7

Start-up

Performance of tasks only by qualified personnel (see
section Qualified personnel).
7.1 Safety instructions for start-up
CAUTION!
Danger from improper operation.
Malfunctions
Before starting, the manual has to be read by the
operator as well as by the responsible technical/
operating personnel and has to be stored at the site of
the compact booster unit at all times.
GB
Adhere to local safety and accident regulations when
starting the compact booster unit.
CAUTION!
Damaged or improperly installed compact booster
unit.
Malfunctions
Check the compact booster unit for obvious signs of
damage; eliminate any defects immediately or alert
the supervising personnel. The compact booster unit
may only be operated in perfect working order.
Inform yourself sufficiently about
the equipment of the compact booster unit
the functionality of the compact booster unit
the close surroundings of the compact booster unit
the measures to be taken in an emergency
7.2 Start-up requirements
CAUTION!
Dry running pump
Damage to the pump/system!
Ensure that there is no water shortage.
The responsible authorities have to be informed
before start-up and before testing.
Before start-up of the compact booster unit, the following
points have to be ensured:
The compact booster unit has to be connected to all
protective equipment according to the regulations.
The relevant VDE and country-specific regulations
have to be adhered to and fulfilled.
Connection of the drinking water inlet is connected to
the drinking water network.
The systems electrical connections have been made
according to regulations
7.3 Fill up and vent the pump and tank
1.
Set the operating mode switch to drinking water inlet
for approx. 15 seconds.
– The system tank is filled automatically.
2.
Open the air bleed valve with a screwdriver or a
square spanner.
3.
Wait until water leaves the air bleed valve.
– When water leaves the air bleed valve, the system
has been vented.
4.
Close air bleed valve.
5.
Draw off water from the system supplied by the CBU
6.
Turn the pump briefly on.
7.4 Switching the system on
The system is automatically turned on, when the mains plug
is inserted.