Device Discovery; System Commands - Balluff BES M12EH1-L01C40B-S04G-L04 Anleitung

Io-link configuration
Vorschau ausblenden Andere Handbücher für BES M12EH1-L01C40B-S04G-L04:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

BES M12EH1-L01C40B-S04G-L04 / BES M18EH1-L01C80B-S04G-L04
Inductive sensors
4
Primary Device Functions (continued)
4.2

Device Discovery

4.2.1
Description
With the Ping function, an IO-Link device can be found
again by starting signaling on the LED of the device by
means of a system command.
4.2.2
ISDU
Name
Index
Ping Timeout
0x00FE (254)
Tab. 4-2:
Device detection – ISDU
Ping Timeout
The Ping Timeout parameter sets the duration of the ping
signal that is displayed via LEDs.
The value is specified minutes. The value range from 0 to
30 minutes is allowed. If the parameter is set to 0, the ping
signal is deactivated. The parameter is reset by Application
Reset and Factory Reset (also see section Reset
Commands on page 79).
4.2.3

System Commands

Command Value
Device Action
0xAF (175)
Start Ping
Tab. 4-3:
Device detection – System Commands
www.balluff.com
Subindex
Access
0
R/W
Length
Data Type
2 bytes
INT
Data
Default
Storage
Yes
1
english
25