Verfügbare Sprachen

Factory
Area
setting
TMax
Yes
Yes, No
TMax
50 °C
30 °C ... 90 °C Maximum temperature of the heating
Remote
No
Yes, No
control
Cooling
No
Yes, No
TCool
16 °C
5 °C ... 25 °C
TMin
No
Yes, No
TMin
10 °C
5 °C ... 20 °C
RH% control
Yes
Yes, No
Chiller option No
Yes, No
Pressure
No
Yes, No
PMin
0,6 bar
0,2 ... 10,0
bar
tMixer
75 s
30 ... 240 s
Corr.tMixer
90 s
5 ... 300 s
tPlay
4 s
1 ... 15 s
Block. prot.
Yes
Yes, No
PWM
Heating Heating, Solar PWM A Curve
Slab drying
-
-
TStart
20 °C
10 °C ... 30 °C Slab drying start temperature
TMax
45 °C
20 °C ... 60 °C Slab drying hold temperature
Rise
5 K
1 ... 10 K
Rise time
24 hours 1 ... 24 h
tBacking
7 days
1 ... 20 d
Start
-
Start, Cancel Slab drying activation/deactivation
Language
Italiano
Deutsch, Eng-
lish, Français,
Italiano,
Español, Por-
tuguês, 中文
10
Meaning
Maximum temperature option for the
heating circuit
circuit
Remote control option
Cooling option
Cooling temperature
Minimum cooling temperature option
Minimum cooling temperature
Dew point detector option (TPS)
Cooling request option on
Low pressure monitoring option
Activation threshold for low pressure
monitoring
Mixing valve operation time
Additional safety time for the mixing
valve closing movement, which is
added to tMixer
First pulse to the actuator when
changing direction
Anti-seizing option
Slab drying submenu
Slab drying rise value
Slab drying rise time
Slab drying hold time
Language selection
Factory
Area
setting
Reset
No
Yes, No
Operation
0
0 ... 9999
Pump
-
0 ... 9999
Mixer Open
-
0 ... 9999
Mixer Closed
-
0 ... 9999
Backup
-
0 ... 9999
heating
S1 value
-
max. 999,9
°C
S2 value
-
max. 999,9
°C
S3 value
-
max. 999,9
°C
Min. press.
-
0 , 0 ... 1 0 , 0
bar
Max. press.
-
0 , 0 ... 1 0 , 0
bar
Version
-
-
Meaning
Reset to factory settings
Operating days of the controller (bal-
ance, the value cannot be reset)
Statistics, these values cannot be
reset (see page 20)
Software version display