Tightening of Connecting Part
1.
Align the centers of the connecting pipes and fully
tighten the flare nut with your fingers. Then fix the
nut with a wrench as shown in the figure and tighten
it with a torque wrench.
Half union or packed valve
Externally
threaded side
Fix with wrench.
Tighten with torque wrench.
2.
As shown in the figure, be sure to use two wrenches
to loosen or tighten the flare nut of the valve on the
gas side. If you use a single crescent, the flare nut
cannot be tightened to the required tightening
torque.
On the other hand, use a single crescent to loosen
or tighten the flare nut of the valve on the liquid side.
Outer dia. of copper pipe
Tightening torque
9.5 mm (dia.)
33 to 42 (3.3 to 4.2 kgf•m)
15.9 mm (dia.)
63 to 77 (6.3 to 7.7 kgf•m)
Cap
Loosened
Valve at gas side
EN-85
Downloaded from
www.Manualslib.com
CAUTION
1.
Do not put the crescent wrench on the cap or cover.
The valve may break.
2.
If applying excessive torque, the nut may break
Flare nut
according to some installation conditions.
Internally
threaded side
NO GOOD
Cap
(Unit: N•m)
• After the installation work, be sure to check for gas
leaks of the pipe connections with nitrogen.
• Pressure of R410A is higher than that of R22 (Approx.
1.6 times).
Therefore, using a torque wrench, tighten the flare
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas
leak, but also trouble with the refrigeration cycle.
Cover
Do not apply refrigerant oil to the flared surface.
Piping valve
Tightened
Flare nut
manuals search engine
- 43 -
Refrigerant Pipe Length
Single
Allowable pipe length (m)
Total length L
50
Gas side
Cover
Ø15.9
Simultaneous twin
Allowable pipe length (m)
Total length
Distributed pipes
1 +
2
2
1 +
3
3
Maximum
Maximum
50
Pipe diameter (mm)
Main pipe
Gas side
Liquid side
Ø15.9
Height difference (Indoor-outdoor H) (m)
Indoor unit: Upper
30
Pipe diameter (mm)
Liquid side
Ø9.5
Figure of Single
Indoor Unit
Outdoor Unit
Height difference (m)
Indoor-outdoor H
Distributed pipes
3 –
2
Indoor unit:
Outdoor unit:
Maximum
Upper
Upper
15
10
30
Branching pipe
Gas side
Liquid side
Ø9.5
Ø12.7
Figure of Simultaneous twin
Indoor Unit
Indoor Unit
Distributor
Outdoor Unit
3
2
1
Outdoor unit: Lower
30
Number of bent portions
10 or less
Indoor-indoor
Δ
(
h)
30
0.5
Number of bent
portions
Ø6.4
10 or less
EN-86