Obstacle in front
Above unit is free
1.
Single unit installation
2.
Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
EN-81
Downloaded from
www.Manualslib.com
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
300 or
more
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
1,000 or
300 or
1,500 or
2,000 or
more
more
more
more
manuals search engine
- 41 -

Installation of Outdoor Unit

• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
Drain nipple
mounting hole
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support the
bottom surface of the fixing leg that is in contact with
and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
300 or
downward piping, consider the piping work.
more
Fixing leg
Foundation
Foundation
200 or
Support the bottom surface of the fixing
more
leg that is in contact with and underneath
the bottom plate of the outdoor unit.
If only the end
of the fixing
leg is
supported, it
may deform.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
• When water is to be drained through the drain hose,
attach the following drain nipple and waterproof rubber
cap, and use the drain hose (Inner dia.: 16 mm) sold
Drain hole
on the market. Also seal knockout hole and the screws
525
securely with silicone material, etc., to prevent water
600
150
from leaking.
Some conditions may cause dewing or dripping of
water.
• When collectively draining discharged water
completely, use a drain pan.
Drain hole
Drain nipple
GOOD
Absorb vibration
with vibration-proof
rubber pads
Knockout hole
For Reference
GOOD
If a heating operation is to be continuously performed for
Bottom plate of
a long time under the condition that the outdoor
outdoor unit
temperature is 0 °C or lower, draining defrosted water
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
NO GOOD
Do not support
the outdoor
unit only with
the fixing leg.
15 or less
Waterproof rubber cap
(5pcs.)
Drain nipple
Waterproof rubber cap
EN-82