Herunterladen Inhalt Inhalt Diese Seite drucken

Symbols In The Document; Intended Use - SMA Sunny Tripower CORE2 STP 100-60 Schnelleinstieg

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 12
SMA Solar Technology AG
Indicates a situation which, if not avoided, can result in property damage.
1.5

Symbols in the Document

Symbol
Explanation
Information that is important for a specific topic or goal, but is not safety-rele-
vant
Section in which the installation and commissioning process is illustrated
graphically.
2
Safety
2.1

Intended Use

The Sunny Tripower is a transformerless PV inverter, with 12 MPP trackers, that converts the direct
current of the PV array to grid-compliant, three-phase current and feeds it into the utility grid.
The product is intended for use in industrial environments.
The product must only be accessible to qualified persons.
The product complies with EN 55011 of class A, group 1:
• a.c. mains power port: ≤ 20 kVA
• d.c. power port: > 75 kVA
• Electromagnetic radiation disturbance: ≤ 20 kVA
In accordance with EN 55011, the product must only be operated at locations where the distance
between the product and third-party radio-communication installations is greater than 30 m. This
distance must be maintained from persons carrying radio or electromagnetically sensitive
equipment.
The product is not intended to be used in living areas and cannot provide protection of radio
reception against interference signals in such environments.
The product is suitable for indoor and outdoor use.
The product must only be operated with PV modules of protection class II in accordance with
IEC 61730, application class A. The PV modules must be compatible with this product.
The product is not equipped with an integrated transformer and therefore has no galvanic isolation.
The product must not be operated with PV modules whose outputs are grounded. This can cause
the product to be destroyed. The product may be operated with PV modules whose frame is
grounded.
All components must remain within their permitted operating ranges and their installation
requirements at all times.
The product must only be used in countries for which it is approved or released by SMA Solar
Technology AG and the grid operator.
Quick Reference Guide
NOTICE
STP100-110-60-IS-xx-11
2 Safety
5

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sunny tripower core2 stp 110-60

Inhaltsverzeichnis