(3) To change the setting, press and hold the SET key for 1 second.
(During this time, the setting in progress indicator lights.)
(4) Use the UP and DOWN keys to select the number of connected units.
Example: If
The setting range is 1 – 64 units (
* T he setting range is different depending on the combination of types.
45.0 kw Type + 45.0 kw Type: up to 52 units (
45.0 kw Type + 56.0 kw Type: up to 59 units (
The range for all other combinations is up to 64 units (
* If there is only one outdoor unit, the setting range is 1 – 50 (
* T he setting range is different depending on the type.
45.0 kw Type: up to 26 units (
56.0 kw Type: up to 33 units (
71.0 kw Type: up to 41 units (
85.0 kw Type: up to 50 units (
(5) Press and hold the SET key for 1 second. (TEST/WARNING turns off.)
(6) Press the HOME key to end the setting process.

8. Setting the System Address and Outdoor Unit Address

* Set the addresses on the outdoor unit control board.
* The system address is set to "1" at the time of shipment.
 Setting the address
(1) Check the wiring condition of the indoor/outdoor control cables.
Outdoor
unit
1-1
(2) Set the system address.
1. Select the
2. Use the UP and DOWN keys to select the system address setting.
Example:
3. To change the setting, press and hold the SET key for 1 second.
(During this time, the setting in progress indicator lights.)
4. Use the UP and DOWN keys to select the system address.
Example: If
The setting range is 1 – 30 (
5. Press and hold the SET key for 1 second. (TEST/WARNING turns off.)
6. Press the HOME key to end the setting process.
(3) Set the outdoor unit address.
1. Select the
2. Use the UP and DOWN keys to select the outdoor unit address setting.
Example:
3. To change the setting, press and hold the SET key for 1 second.
(During this time, the setting in progress indicator lights.)
is displayed, pressing the UP key displays
Outdoor
unit
1-2
Indoor/outdoor control cable
Refrigerant tubing
Indoor
Indoor
Indoor
unit
unit
unit
(initial settings) menu item to display
(System address is 1.)
is displayed, pressing the UP key displays
(initial settings) menu item to display
(Outdoor unit address is 1.)
-
).
)
)
).
)
)
)
)
Outdoor
unit
2-1
Indoor
Indoor
unit
unit
Fig. 3
-
).
EN - 8
.
-