13. Test Run Settings

* When a test run is performed using the control board of the outdoor unit with the smallest address, the test run is performed
for all outdoor units connected to the same refrigerant tubing system.
* You can cancel a test run from the control board of the outdoor unit with the smallest address.
(1) Select the
(2) Press the SET key to change to the following display.
Example:
(3) Use the UP and DOWN keys to select the following settings: forced cool test run, forced heat test run, forced valve operation,
forced water circulation, and forced bypass valve closing.
Table 5
DOWN
UP
13-1. Setting outdoor unit trial run and forced outdoor unit operation
Forced cool test run setting
 With the forced cool test run setting selected, press and hold the SET key for 1 second to perform a forced cool test run.
During this time, the setting in progress indicator lights.
Forced heat test run setting
 With the forced test run setting selected, press and hold the SET key for 1 second to perform a forced heat test run. During
this time, the setting in progress indicator lights.
Forced valve opening (Use when applying vacuum.)
 With the forced valve opening setting selected, press and hold the SET key for 1 second to operate the valves.
The indoor unit solenoid valve, outdoor unit solenoid valves (2), liquid valve, and bypass valve open all the way. During this
time, the setting in progress indicator lights.
 All the outdoor units connected to the same refrigerant system are set to forced valve opening.
When the individual outdoor unit has to be configured, it must be separated from the system.
(test run, forced outdoor unit operation setting) menu item to display
(forced cool test run setting)
Display
Forced cool test run
Forced heat test run
Forced valve opening
Forced water circulation
Forced bypass valve closing
Automatic air release mode
EN - 13