Important Information Regarding the Refrigerant Used
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
Refrigerant type: R410A
GWP
value: 2088
(1)
GWP = global warming potential
(1)
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your
local dealer for more information.

1. Precautions

Using the level, check that the installation of the outdoor unit is horizontal. If not, this may result in failure.
To operate the system, individual addresses must be set for the outdoor and indoor units.
The outdoor unit address must be set manually; however, the indoor unit addresses are set automatically for each refrigerant
system.
After the addresses are set, the indoor unit addresses must be checked in order to identify each indoor unit.
After the addresses have been checked, apply unit number labels to each indoor unit and outdoor unit. These will be necessary
for later maintenance.
Follow the procedure below and perform the work correctly.

2. Test Run Procedure

Start
Set the type of fuel gas. (For Band P (LPG))
Check the date and time
Check the initial settings ((1) Model, (2) Power).
Check and set the type of engine gas
(Supplied as fuel).
Set the number of connected indoor units.
Check wiring arrangement of control cables
between indoor and outdoor units.
Set the outdoor unit address.*
(*The address indicates the unit serial number.)
Set final terminator status.
Re-check the pre-test run check items.
• Check the following before performing a test run.
Ensure that tube connections are securely attached, and that
there are no leaks.
Ensure that shut-off valves (service valves) are open.
If a compressor is run while a shut-off valve (service valve)
is closed, the pressure will become abnormally high and
there is a risk of damage to the parts of the compressor, etc.
Additionally, if there is a leak in the connection parts, the
pressure will become even more abnormally high because of
sucked-in air, etc. and there is a risk of rupturing and injury.
Section
3
Section
4
Section
5
Section
6
Section
7
Section
8
Section
8
Section
9
Section
10
Check the refrigerant tubing and control cables
for outdoor units.
Set the indoor unit addresses (automatic addresses).
Check the indoor unit addresses.
(If necessary)
Change indoor unit addresses.
Test run
Does system operate?
Return remote control
to normal mode.
End
EN - 3
Section
11
Section
12
Section
15
(*Using remote controller)
Section
16
(*Using remote controller)
Section
13
No
Section
14
Check and correct using
the self-diagnosis
function table.
(Note: Check the indoor-side drainage.)