Herunterladen Inhalt Inhalt Diese Seite drucken

Shorten The Connection Cable - STG-BEIKIRCH CDs Technische Information Und Bedienungsanleitung

Rwa kettenantrieb
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7.4

Shorten the connection cable

Required tools and electrical accessories:
Montageablauf:
1 Öffnen Steckergehäuse
mit Schraubendreher für
1
Totx T10 Schrauben
Remove screws on connector housing
with Torx-screwdriver (T10).
2
Position the slot-screwdriver on the
side groove at point A and pry up the
connector housing.
3
Remove housing upper shell.
4
Remove the wires individually from the
plug-in terminal with a screwdriver.
Press in the terminals using the
screwdriver.
2 Adern aus Push-In-Klemme
entfernen
5
Cut the connection cable, strip approx.
45 mm and provide the individual wires
3 Abmanteln und abisolieren der Verbindungsleitung
with ferrules. Then insert the wires with
ferrules into the plug-in terminal
according to numbers:
No. Wire colour Wire profil
1
white
0.75 mm²
2
brown 0.75 mm²
3
green
0.25 mm²
4
yellow 0.25 mm²
5
grey
0.25 mm²
6
pink
0.25 mm²
6
Insert the plug-in terminal with the
4 Angeschlossene Push-In-Klemme
connecting cable with the numbers
in Gehäuseunterschale des Steckers
above into the guide of the
in die dafür vorgesehene Nuten
housing lower shell. The cable sheath
einlegen.Dann Oberschale
must be in the strain relief. Then fit the
festschrauben.
upper shell in the correct position and
lock in place.
7
Screw connector housing with Torx
screws.
04/13424999257
Torx-screwdriver (T10), slot-screwdriver
2 x ferrules 0,75 mm² (long), 4 x ferrules 0,25 mm² (long)
1
3
5
45
6
Numbers
above!
Housing lower shell
Torx-screwdriver (T10)
2
4
Housing upper shell
Plug-in terminal
Connection cable
1 2 3 4 5 6
Insulated ferrules 0.75 x 10
(for wires color white and brown)
Insulated ferrules 0.25 x 8
(for remaining wires)
7
Strain relief
SHE chain drive CDs
A
Slot-screwdriver
45
33