Safety controlgears
Instructions
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
AND BURNS.
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
Application
You can use the safety controlgears C571/C573 in EMERGENCY STOP
devices as per EN 418 and in safety circuits as per VDE 0113 Part 1 (11.98)
and/or EN 60 204-1 (11.98), e.g. with movable covers and guard doors.
Depending on the external connections, categories 3 and 4 (with additional
external measures) as per DIN EN 954-1 are achievable.
Functions and connections
The safety controlgear C573 has three release circuits (safety circuits)
which are configured as NO circuits and a signal circuit configured as an
NC circuit.
The safety controlgear C571 has two release (safe) circuits which are confi-
gured as NO circuits. The number of release circuits can be increased by
adding one or more C579 expansion units. Three LEDs indicate the opera-
ting state and function.
When the EMERGENCY STOP button or the limit switch is unlocked and
when the ON button is pressed, the internal circuits of the safety controlge-
ars and the external contactors are checked for proper functioning.
Connect the EMERGENCY STOP pushbutton or the limit switch in the supply
cable from A1 to +24 or L24 V. To evaluate over two channels, connect
Channel 2 from A2 to 0 V or N. Connect the ON button in series with the NC
contacts of the external contactor (feedback circuit) to terminals Y1 and 2
(for circuit examples, see Figs. IV to VII).
Terminal
Operating
A1
assignments
voltage
A2
Sensors
Y1, 2
Outputs
13, 14
23, 24
33, 34
41, 42
2
Cable lengths
for 2 x 1.5 mm
150 nF/km
Figures
Fig. I:
Dimension drawings (dimensions in mm)
Fig. II:
Installation
Internal circuit: ¿ PTC fuse, À power pack,
Fig. III:
Á control logic, Â Channel 1, Ã Channel 2
Fig. IV:
EMERGENCY STOP, category 2 per EN 954-1
Fig. V:
EMERGENCY STOP, category 3 and 4 per EN 954-1
Fig. VI:
Guard door monitoring, category 2 per EN 954-1
Fig. VII: Guard door monitoring, category 3 and 4 per EN 954-1
2
L/+
N/-
ON button, feedback circuit
Release circuit 1 (NO)
Release circuit 2 (NO)
Release circuit 3 (NO)*
Signal circuit (NC)*
* with C571 only
max. 1000 m (total cable length for
sensors and power supply lines)
DIN EN 60 439 Part 1, VDE 0660 Part 500 (04.94)
Order No.: 1SAC 105 398 S4001
Operating states
LEDs
POWER Channel 1 Channel 2 PS
Fault
1. Switch supply voltage off.
clearance
2. Clear fault or replace device.
3. Switch supply voltage back on.
Technical data
Permissible ambient temperature T u
Operation/storage
Degree of protection to EN 60 529
Rated insulation voltage U i
Rated impulse withstand voltage U
Rated control supply voltage U s
Rated power
DC operating range
AC operating range
Shock resistance (half-sine) as per IEC 60068
Weight
Recovery time
Release time
Response time
Utilization
Rated operational
category
voltage U
e
(V)
as per DIN VDE 0660
Part 200, IEC 60947-5-1
AC-15
230
DC-13
24
115
230
Continuous current I
th
Short-circuit
protection
Fuse links
for release circuit
Duty class
and signal circuit
Duty class
Control supply voltage
The safety controlgear is protected by an internal self-healing
PTC fuse (multifuse).
Be sure to fit the specified fuses. Otherwise safe interruption
in the event of a fault cannot be guaranteed.
For further data and accessories see Main Catalog, Part 1.
C571, C573
English
Operation
EMERGENCY
ON
STOP
ON
not activated activated
activated
not activated open
not activated not activated open
Faults
• Relay fusion-welded
• Motor contactor fusion-welded
• Defect in electronics
Cross or ground faults in
EMERGENCY STOP circuit (min.
fault current I
= 0.5 A; PTC fuse
Kmin
trips or supply voltage missing)
-25 to +60°C/-40 to +80°C
IP 40, IP 20 at terminals
300 V
4 kV
imp
24 V AC/DC
1.5 W
0.85 to 1.2 x U s
0.85 to 1.1 x U s
8 g/10 ms
0.240 kg
minimum 200 ms
max. 150 ms
max. 200 ms
Rated operational current I
with all release circuits loaded
(A)
50 °C
60 °C
5
4.5
5
4.5
0.2
0.2
0.1
0.1
5
4.5
DIAZED
gL(gG) 6 A / quick response 10 A
gL(gG) 6 A / quick response 6 A
gL(gG)
2 A
Release
circuits
closed
open
e
70 °C
4
4
0.2
0.1
4

Werbung