DANSK
Trykstyret pilotventil
Konstruktion
Se fig. 1, 2 og 3.
43. Pakning
44. Blændprop for manometertilslutning
81. Pakning
82. O-ring
103. Banjofitting
104. O-ring
105. Dækhætte
106. O-ring
107. Signaltilslutning
108. Pilotdyse
109. Studs på banjofitting
110. Membran
111. Fjeder
112. Indstillingsspindel
Tekniske data
CFC, HFC, HCFC og
Kølemidler
R 717 (NH
–0.45 bar g til 7 bar g
Reguleringsområde
(13.3 in. Hg til 102 psig)
Fabriksindstilling
Helt slap fjeder
–50°C til +120°C
Medietemperaturområde
(–58°F til 248°F)
Maks. driftstryk
17 bar g (247 psig)
Maks. prøvetryk
28 bar g (406 psig)
Montering
CVC
monteres
i
PM/PMC
topdæksel; se fig. 5 og 7. Kontrollér, at pakningen
(81) og O-ringene (82 og 104) er på plads og i
orden – O-ringen (82) smøres med fryseolie; se
fig. 1.
NB! Hvis O-ringen (82) er utæt eller mangler helt,
vil hovedventilen få signal til at åbne.
Banjofittingen (103) kan drejes. Tilspændingen
bør ske med et moment på 50 Nm (5 kpm).
Nøglevidden er 32 mm.
Banjofittingen er forsynet med to ens tilslutnings-
huller.
I det ene hul monteres signalledningen ved hjælp
af tilslutningen fig. 3. Signalledningen fra CVC
skal tilsluttes der hvor trykket ønskes reguleret,
f.eks. umiddelbart før kompressoren, hvis der
ønskes en startregulatorfunktion.
Signalledningen må ikke kunne afspærres.
I det andet hul på banjofittingen er det muligt
at tilslutte et manometer, der kan anvendes ved
indstillingen af CVC. Manometeret måler trykket
P
i signalledningen. I stedet for blændproppen
s
(44) skal der så iskrues en manometertilslutning,
fig. 2 eller 3; se »Tilbehør«.
Hvis kun den ene af banjofittingens to
tilslutnings-huller bruges, skal det andet blændes
af med blændproppen (44).
CVC kan desuden monteres i ventilhuset CVH
og anvendes som separat pilotventil eller
selvstændig ventil; se fig. 4.
Anvendes CVC-CVH som separat pilotventil,
skal enheden monteres i pilotledningen med
gennem-strømning imod hovedventilen.
Indstilling
Pilotventilen åbner ved faldende tryk p
ledningen.
Drejes indstillingsspindelen (112) med uret (højre
om), hæves åbningstrykket – og omvendt.
En omdrejning af indstillingsspindelen ændrer
åbningstrykket ca. 1.5 bar.
Grovindstilling
Drej spindelen (112) mod uret til stop. Drej
derefter med uret det antal omdrejninger, der
svarer til det ønskede åbningstryk.
Finindstilling
Indstil ved hjælp af manometer.
Service
Dysen i CVC kan renses med trykluft. Skru CVC
af og træk reguleringsdelen ud af banjofittingen
(103). Drej spindelen (112) med uret, indtil
pilotventilen er helt åben. Gennemblæs dysen
(108) med trykluft imod normal gennemstrømn
ingsretning.
Undersøg og udskift eventuelt O-ringene (82
og 104).
Reservedele
Se Spare Parts katalog.
Tilbehør
Manometertilslutning
for fluorerede kølemidler: selvlukkende ventil
med
flaretilslutning
027B2041; for ammoniak: ∅6.5 / ∅10 mm
svejsestuds (fig. 3) bestillingsnr. 027B2035.
)
CVH pilotventilhus
3
Se hovedkataloget.
Pressure-controlled pilot valves
Design
See fig. 1, 2 and 3.
43. Gasket
hovedventilens
44. Blanking plug for manometer connection
81. Gasket
82. O-ring
103. Banjo fitting
104. O-ring
105. Seal cap
106. O-ring
107. Signal connection
108. Pilot orifice
109. Connector on banjo fitting 103
110. Diaphragm
111. Spring
112. Setting spindle
Technical data
Refrigerants
Regulating range
Factory setting
Media temperature range
Max. working pressure
Max. test pressure
Fitting
CVC is fitted in the top cover of the PM/PMC
main valve, see figs. 5 and 7. Check that gasket
(81) and O-rings (82 and 104) are in place and in
order – the O-ring (82) must be lubricated with
refrigeration oil, see fig. 1.
NB: If O-ring (82) is leaking or missing, the main
valve will receive a signal to open.
Banjo fitting (103) can be turned. Tightening
should be made to a torque of 50 Nm (37 lb force
i signal-
s
ft) with a 32 mm wrench.
The banjo fitting has two identical connection
holes.
In the one hole the signal line is fitted with the
connection shown in fig. 3. The signal line from
the CVC must be connected at the point where
the pressure is to be regulated, e.g. immediately
in front of the compressor if crankcase pressure
regulator function is required.
It must not be possible to block the signal line.
RI09U152 → RI4XL152 © Danfoss A/S (RC-CMS), 11-2004
(fig.
2)
bestillingsnr.
ENGLISH
CFC, HFC, HCFC and
R 717 (NH
)
3
–0.45 bar g to 7 bar g
(13.3 in. Hg to 102 psig)
Completely slack spring
–50°C to +120°C
(–58°F to 248°F)
17 bar g (247 psig)
28 bar g (406 psig)
In the other hole in the banjo fitting a mano-
meter can be fitted for use when setting CVC.
The manometer measures the pressure p
the signal line. Instead of blanking plug (44)
a manometer connection, fig. 2 or 3, must be
screwed in, see „Accessories".
If only one of the two connection holes in the
banjo fitting is used the other must be blanked
off with blanking plug (44).
CVC can also be fitted in valve body CVH and be
as a separate pilot valve or independent valve,
see
fig. 4.
If CVC-CVH is used as a separate pilot valve the
unit must be fitted in the pilot line with flow
towards the main valve.
Setting
The pilot valve opens at a fall in pressure p
signal line.
Turning the setting spindle (112) clockwise raises
the opening pressure and vice-versa.
One turn of the setting spindle changes the
opening pressure by approx. 1.5 bar (21.8 psi).
Rough setting
Turn the spindle (112) counterclockwise to stop.
Then turn it clockwise for the number of turns
corre-sponding to the desired opening pressure.
Fine setting
Set with the aid of a manometer.
Service
The orifice in CVC can be cleaned with
compressed air. Screw off the CVC and draw the
regulation part out of the banjo fitting (103).
Turn spindle (112) clockwise until the pilot valve
is fully open. Blow compressed air through orifice
(108) in the opposite direction to normal flow.
Examine O-rings (82 and 104) and replace if
necessary.
Spare parts
See Spare Parts catalogue.
Accessories
Manometer connection
For
fluorinated
refrigerants:
valve with flare connections (fig. 2) code no.
027B2041;
for ammonia: ∅6.5 / ∅10 mm welding
connectors (fig. 3) code no. 027B2035.
CHV pilot valve body
See Main Catalogue.
in
s
in the
s
self-closing
3