Herunterladen Diese Seite drucken

Emerson EC3-X32 Betriebsanleitung Seite 3

Überhitzungsregler mit tcp/ip schnittstelle
Vorschau ausblenden Andere Handbücher für EC3-X32:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
Code
Parameter description and choices
b1 Battery error management, when battery is
defective, see below
Alarm
value
display
Alarm relay
0
-
1
Ab
2
Ab
Signaling
3
Ab
Signaling
(blinking)
When setting b1 to option 0 or 1, the user must ensure appropriate safety
!
precautions are in place to protect the system against damage caused by
a power failure.
uF Control range valve %
*) Notes for R32: R32 is classified as low flammable refrigerant in Europe. EC3-
X32 is designed under consideration of European safety standards and directives for
none flammable refrigerants. The use of EC3-X32 with R32 is for systems/regions
which it does not require consideration of additional safety standards as for
flammable refrigerant.
After selecting the parameters the EC3-X32 is fully functional without connected PC
or keypad/display unit ECD-002.
C o n t r o l ( v a l v e ) s t a r t - u p b e h a v i o r : ( P a r a me t e r u u a n d u 9 )
EX4/5/6 ≤ 1.5 seconds
EX7 ≤ 3.2 seconds
uu
EX8 ≤ 7.2 seconds
≤ 7.3 seconds
FX5-8
FX9 ≤ 9.7 seconds
P u m p d o w n f u n c t i o n : ( i f P 6 = 1 a n d L 2 = 1 )
Digital input
Alarm
status
condition
24V (ON)
NO
0V (OFF)
NO
0V or 24V
YES
P o s s i b i l i t i e s o f c o n n e c t i n g E C 3 - X3 2 t o a n e t w o r k o r P C :
• A TCP/IP Controller Readme file is available on the
website to provide detailed information about TCP/IP Ethernet connectivity.
Please refer to this file if you need information beyond the contents of this
instruction sheet.
• Connect the EC3-X32 using the optional ECC-Nxx cable assembly or a standard
CAT5 network cable with RJ45 plugs assembly to a network or router that enables
the controller to receive a dynamic TCP/IP address or
• Connect the EC3-X32 to a computer using a crossover cable plugged directly into
the Ethernet port. In this case, the TCP/IP address of the computer must be
manually modified to be compatible with the default address of the controller.
Refer to the TCP/IP Controller-Readme file for more details.
S e t t i n g a n d v i s u a l i z i n g D a t a : W e b P a g e s
(recommended method)
• Make sure that digital input is 0V (open), turn the power supply ON.
• Four parameters i.e. refrigerant type (u0), pressure sensor type (uP), valve type (ut)
and control mode can be set only when digital input is open (0V) while the power
supply is ON (24V). This feature is for added safety to prevent accidental damage
of compressors and other system components. All other parameters can be
modified at any time.
• The EC3-X32 has a TCP/IP Ethernet communication interface enabling the
controller to be directly connected to a network or a PC via the standard Ethernet
port. The EC3-X32 controller has embedded WebPages to enable the user to
visualize the parameter lists using real text labels.
• To view WebPages on the PC, a standard Web Browser like Internet Explorer® or
Mozilla Firefox and JRE Java Runtime Environment is needed. JRE can be
downloaded at no charge from the
• Open the Internet browser program on the computer and, if EC3-X32 is connected
directly to PC with a crossover cable enter the default TCP/IP address of the
controller (192.168.1.101) into the address line, or the dynamic address from the
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
EC3-X32 Superheat Controller with TCP/IP
communication capability
Factory
Min Max
setting
0
3
Reset possibility after
Valve
recovery/replacement
-
Regulating
-
Regulating
Fully close
Fully close
5
100
100
%
Sec.
u9
Pump down relay
Activate
Deactivate when pressure drops
below P7 and after elapsed time P8
Deactivate
www.emersonclimate.eu
www.java.com
website.
www.emersonclimate.eu
Operating instruction
DHCP server from network/Router. Refer to the TCP/IP Controller-Readme file
if a specific port is required.
Field
• It is possible to identify the dynamic TCP/IP address assigned by DHCP of the
setting
Router or network, refer to the TCP/IP Controller-Readme file.
2
• After a few moments, the default monitoring page should be displayed. If the
browser does not open the default page or display active data, the user should check
the Internet browser "Option" configuration. Refer to the TCP/IP Controller-
Readme file.
-
-
Auto
Manual
• The Monitoring and Alarm WebPages are read only and therefore it is not
necessary to enter a username or password. A username and password will be
requested upon the initial request to any of the other WebPages. The factory default
settings are: Username: "EmersonID", Password: "12"
• The default settings may be modified on the Display configuration page.
• Press the tabs at the top of the Monitoring page with a left click of the mouse button
to enter the respective Webpage.
• The parameters will be visualized in real text together with the program code as
defined in the parameter list below.
• After the parameters have been modified, the complete list of settings can be saved
to the memory of the computer and used later to upload into another controller.
This can save a considerable amount of time when using multiple controllers and
over a period of time, a library can be created containing the parameter lists for
equipment for different applications.
• It is also possible to display live graphical data from the controller. Superheat,
evaporating pressure, coil-out temperature and evaporating temperature are
available on a 15 minutes rolling chart. Refer to the TCP/IP Controller-Readme
file for a complete description of the features available for the TCP/IP series of
controllers.
Date: 03.04.2017
EC3-X32_OI_ML_R13_865008.docx

Werbung

loading