Do not touch any of the Fan moving parts.
Fancom advises to leave the Fan on for about 6 hours after installation, to let it run in.
The Fan requires no specific maintenance. Fancom recommends that your installation technician inspects the
complete climate installation, of which the Fan is a component, every half-year.
Inspect the Fan periodically for any damages. Notify your installation technician immediately of any
damages. A damaged Fan is unsafe!
Check the Fan for proper functioning regularly.
There must always be power to the Fan. This prevents the formation of condensation in the Fan.
The Fan may be cleaned wet, but consider the following:
Do not use a high pressure hose or aim at motor seals or openings at close range.
The fan should be turning. This makes for a better seal at the shaft ends and prevents water flowing
into the motor. It is recommended that the fan turns at 50%. If so, water will be discharged faster by
the airflow.
This fan has protection class IP66.
After cleaning the Fan, it should run at 100% rpm for at least 30 minutes to remove all dampness.
When disposing the Fan please comply with all relevant requirements and regulations applicable in your country.
See the ID label on the motor for additional information. Also see detailed specifications and fan
characteristics for each type at www.fancom.com/uk/downloads or the Fancom extranet.