The enclosed documentation is an integral part of the product. The documentation must be read, observed and stored in
a place which is freely accessible at all times.
The name plate must be permanently attached to the product.
Any other or additional use of the device shall be regarded as improper.
This includes:
ž Use of a distribution system that is not described (grid type)
ž Use of sources other than PV-strings.
ž Mobile use
ž Use in rooms where there is a risk of explosion
ž Use in direct sunlight, rain or a storm or other harsh environmental conditions
ž Outdoor use in environmental conditions that exceed the limits stated in the technical specifications >Environmental
data [See section 4.3} Page 11].
ž Operation outside the specification intended by the manufacturer
ž Modifying the device
ž Standalone mode
2.2

Protection features

The following monitoring and protection functions are built-in:
ž Overvoltage conductor / varistor to protect the power semiconductors from high-energy transients on the grid and
generator sides.
ž Device temperature monitoring system
ž EMC filter to protect the inverter from high-frequency grid interference
ž Grid-side varistors grounded to earth to protect the product against burst and surge pulses
ž Anti-islanding detection according to the current standards.
ž ISO/AFI detection of a generator insulation fault.
NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact
on the electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installa-
tions- Part 6: Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an
overvoltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.
3

Description of the device

3.1

Mode of operation

The device converts the DC voltage generated by the PV-modules into AC voltage and feeds this into the power grid. The
starting procedure begins when there is sufficient sunlight and a specific minimum voltage is present in the device. The
feed-in process begins once the PV generator has passed the insulation test and the grid parameters are within the re-
quirements imposed by the grid operator for a specific monitoring time. If, as it gets dark, the voltage drops below the
minimum voltage value, feed-in mode ends and the device switches off.
Page 8
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanaet 150 TL3