General information and technical data:
Pressure Transmitters convert a pressure into a linear
electrical output signal.
PS:
Type
Range
Max.
working
bar
Pressure
PT5-07M/T
-0.8...7
27 bar
PT5-18M/T
0 ... 18
45 bar
PT5-30M/T
0 ... 30
45 bar
PT5-50M/T
0 ... 50
72 bar
• All pressures are gauge pressure
• Supply voltage: 7 ... 30V DC, class 2
• Permissible noise & ripple: < 1 V
• Dimensions (mm) see Fig. 2 - 4
• CE-mark under EC Directive 2004/108/EEC &
EN61326
• Marking:
• Protection (EN 60529) IP65 (with connector PT4-
Mxx)
PT5__65158__R00.doc
www.emersonclimate.eu
!
• Read
Failure to comply can result in device failure,
system damage or personal injury.
• It is intended for use by persons having the
appropriate
attempting to install the PT5 make sure
pressure in system is brought to and remains at
atmospheric pressure.
• Do not exceed the specified voltages and
pressures.
• Do not use any other fluid media without prior
approval of EMERSON.
• Compliance with local electrical regulations
when wiring.
• Electronic devices are subject to electro
PT:
magnetic
Test
components in the system are sufficiently
pressure
protected.
Installation
30 bar
Mounting position: as desired. In order to prevent
50 bar
ice build-up and or condensation on the PT5 when
50 bar
connected to the suction pipe, it is sometimes useful
80 bar
to extend the connection using a nominal 200mm
piece of 6mm/1/4" copper tube from the main
suction pipe (Fig.5).
Flare Connections: PT5-xxM Series
p-p
• Do not exceed max. torque of 20Nm for
tightening
connection.
Warning: If a leak is detected at the specified
torque, the flare surface of the Schrader connector
should be checked for scratches. Do not over
torque; instead, insert a copper gasket.
Replacement for : -
Installation Instructions
Pressure Transmitter PT5-xxM & PT5-xxT
Safety instructions:
installation
instructions
thoroughly.
knowledge
and
skill.
interference.
Ensure
of
PT5
to
Schrader
Date: 06.05.2010
Braze Connections: PT5-xxT Series
The Stainless Steel tube connection does not
require any wet rag during brazing. It is important
to consider the following subjects:
- Use of flux and silver rod having a minimum
of 30% silver.
Before
- Direct torch away from transmitter as shown in
Fig. 6. Max. body temperature: 120°C
Leakage Test:
• After completion of installation, a test pressure
must be carried out as follows:
- According to EN378 for systems which must
comply with European pressure equipment
directive 97/23/EC
- To maximum working pressure of system for
non European installations.
that
all
Wiring (Fig. 1):
For proper wiring use cable assembly (PT4-Mxx).
Allow enough space on top of pressure transmitter
to mount plug as shown in Fig. 4. The plug can be
mounted on pressure transmitter only in one
position Fig 1: (1).
Cable Colour Code and Pin Connection
Part
PT4-Mxx
(Plug/Cable)
Note 1: In case electrical connection cable is
pressure
extended beyond 6 m, system signal noise and EMC
must be verified by installer for proper operation.
Note 2: Signal line should not be installed parallel
with power lines to avoid electrical interference.
GB
Supply,
Signal,
+24Vdc
4-20mA
Pin 1:
Pin 2:
Brown wire
White wire
PCN 865885