Herunterladen Inhalt Inhalt Diese Seite drucken

Mounting; Preparing Mounting; Installing The Circulation Pump - AFRISO PrimoTherm 180-1 DN25 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für PrimoTherm 180-1 DN25:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5

Mounting

Unless otherwise specified, all information on mounting relates to the instal-
lation type "flow right". Conversion is described in chapter "Interchanging
flow/return" on page 20.
5.1

Preparing mounting

Only mount the product after having completed all pipe assembly work, all
welding work and all soldering work.
Flush the lines of the system before installing the product.
If you install the product in an existing system, observe the information in
chapter "Retrofitting the product" on page 24.
5.2

Installing the circulation pump

If you use a product version without pre-assembled circulation pump, you
must install a suitable circulation pump with a length of 180 mm yourself.
 Verify that you use the seals enclosed with the product.
1. Observe the specifications of the pump manufacturer.
2. Mount the pump.
- Connection thread G1½, tightening torque 60 Nm.