11 Technical data

Uponor Climate Controller C-46
Item
CE marking
IP
Degree of protection
Low voltage tests
EMC (electromagnetic compatibility) tests
ERM tests (electromagnetic compatibility and
radio spectrum matters)
Home and building electronic systems (HBES)
Power
Power consumption
Operating temperature
Storage temperature
Maximum ambient RH (relative humidity)
Sensor inputs
General purpose input
General purpose output
Thermal actuator output
Motorized valve output
U P O N O R C L I M AT E C O N T R O L L E R C - 4 6 - Q U I C K G U I D E
Description
Power-on indicator
IP30 (IP: degree of inaccessibility to active parts of the product and degree of water)
IK04
EN 60730-1* and EN 60730-2-1**
EN 60730-1 and EN 301-489-3
EN 300 220-3
50090-2-2, part 2-2: System overview - General technical requirements
230 V AC +10/-15 %, 50 Hz, wires < 1.5 mm²
19 W maximum
0 °C to +55 °C
-20 °C to +70 °C
95 % maximum at 20 °C
Four analog inputs for NTC temperature sensors, 2 wires, < 1.5 mm², < 4 m
Only dry contact, 2 wires, < 1.5 mm², < 20 m
Galvanic isolated dry contact 24 V AC, 1 A maximum
Minimum switching capacity: 100 mA, 5 V DC, 2 A circuit breaker recommended
2 wires, < 1.5 mm², < 20 m
24 V DC ±10%, 300 mA maximum, short circuit protected (one valve only)
2 wires, < 1.5 mm², < 0.75 m
0–10 V DC, short circuit protected, 2 wires, < 1.5 mm², < 20 m