Coeffi Cienti Correttivi Per Fattori • Di Sporcamento Evaporatore; Water Circuit Pressure Drops; Evaporator Water Fl Ow Limits; Correction Factors - MAXA HWA-A/FC 06205 Technisches Handbuch

Luft/wasser flüssigkeitskühler mit axiallüftern und scroll verdichtern von 205kw bis 1085 kw
Inhaltsverzeichnis

Werbung

PERDITE DI CARICO CIRCUITO IDRAULICO

LIMITI PORTATA ACQUA EVAPORATORI
Modello
06205 06232 06259 06286 08323 08360 08395 10434
Portata minima
l/s
5,8
6,5
Portata massima l/s
15
17
FATTORI DI CORREZIONE
Alla macchina, funzionante con una soluzione acqua/glicole,
vanno ap pli ca ti i seguenti fattori correttivi.
Percentuale di glicole etilenico
in peso (%)
Temperatura di congelamento (°C)
Coeff.corr. resa frigorifera
Coeff.corr. potenza assorb.
Coeff.corr. portata miscela
Coeff.corr. perdita di carico
Moltiplicatore di resa Free-Cooling
COEFFICIENTI CORRETTIVI PER FATTORI DI
SPORCAMENTO EVAPORATORE
0
Evaporatore pulito
0,44 x 10
-4
(m2 °C/W)
-4
0,88 x 10
(m2 °C/W)
1,76 x 10
-4
(m2 °C/W)
f1: fattori di correzione per la potenza resa
fp1: fattori di correzione per la potenza assorbita dal compressore;
Le prestazioni delle unità indicate nelle tabelle vengono fornite
per le condizioni di scambiatore pulito (fattore di sporcamento =
0). Per valori differenti del fattore di sporcamento, le prestazioni
fornite dovranno essere corrette con i fattori indicati.
5
7
8
6,8
7,7
8,6
10
10
18
21
22
25
27
0
10
0
-4,5
1,075
1,048
1,01
1,006
0,88
0,92
0,791
0,855
1,095
1,071
HWA-A/FC 06205÷121085

WATER CIRCUIT PRESSURE DROPS

10
12
14
16 18
20
q
10476
12528
12581
12655
15
16
11
12
13
31
33
35
40
45

CORRECTION FACTORS

The machine, operating with a glycol/ water solution, the following
correction factors should be applied to any calculations.
20
30
40
-9,5
-15,5
-21,5
1,021
1
0,978
1,002
1
0,998
0,96
1
1,01
0,942
1
1,082
1,045
1
0,943
EVAPORATOR FOULING FACTOR
CORRECTIONS
f1
fp1
1
1
0,98
0,99
0,96
0,99
0,93
0,98
f1:
capacity correction factors
fp1: compressor power input correction factor Unit performances
reported in the tables are given for the condition of clean exchanger
(fouling factor = 0). For different fouling factors values, unit
performances should be corrected with the correction factors
shown above.
27
25
30
40
EVAPORATORS WATER FLOW LIMITS
12727
12815
12906 121000 121085
20
25
25
30
50
55
65
70
Ethylene glycol percent by
50
weight (%)
Freezing point (°C)
-32,5
Cooling capacity corr. factor
0,946
Power input corr. factor
0,995
Mixture fl ow corr. factor
1,04
Pressure drop corr. factor
1,154
Effi ciency multiplier in Free Cooling
0,874
0
Clean evaporator
0,44 x 10
(m² °C/W)
-4
0,88 x 10
(m² °C/W)
-4
1,76 x 10
(m² °C/W)
-4
50
60
70
80
Model
Minimum fl ow
30
Maximum fl ow
70