Herunterladen Diese Seite drucken

Startup; Operation - Grundfos MP 204 Montage- Und Betriebsanleitung

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 74

9. Startup

A basic setting of MP 204 can be made on the
operating panel.
Additional functions must be set with Grundfos GO
Remote or PC Tool Water Utility.

9.1 Operation

Pos. 1
Pos. 2
Pos. 3
Pos. 2
Pos. 4
Fig. 14
Operating panel
"Power"
Pos. 1
indicator light
"Trip" indicator
Pos. 2
light
Pos. 3 Display
Pos. 4 IR field
Operating
Pos. 5
buttons
9.1.1 Button (Test)
Press the
button to open trip relay connection
95-96 and close signal relay connection 97-98. The
red "Trip" indicator light is on. The function is
identical to the overload trip.
9.1.2 Button (Reset)
R
Press the
button to change the tripped state to
normal state with trip relay connection 95-96 closed
and signal relay connection 97-98 open. The red
"Trip" indicator light is off. This implies that the
tripped state has actually ceased. The
also resets warnings, if any.
16
MP 204
Pos. 5
Flashes green until
MP 204 is ready for
operation (power-on
delay).
Is permanently
green when MP 204
is ready for
operation.
Flashes red when
communicating with
Grundfos GO
Remote.
Is red when the trip
relay is activated.
4 digits, for basic
setting and data
reading.
Grundfos GO Remote
communication.
R
Setting and operation.
R
button
9.1.3 Button (+)
Normally the actual current or temperature appears
on the display. Press the
information on the display, according to the following
sequence:
Trip code (flashing)
Warning code no. 1-n
Current
Voltage
Temperature Tempcon
Temperature Pt sensor
Phase angle cos φ
Fig. 15
Sequence on the display
The trip code only appears if MP 204 has tripped.
Switches between "trip" and trip code.
The warning code only appears if the limit value
of one or more warnings has been exceeded, and
if warning code indication has been activated.
Temperatures only appear if the matching
sensors have been connected and activated. If
no Tempcon signal is received, "----" appears on
the MP 204 display.
Cos φ only appears if this menu has been
enabled with Grundfos GO Remote.
When the motor is operating, the display shows the
actual value.
When the motor stops, the display shows the last
measured value.
9.1.4 Button (-)
Only used in connection with the basic setting of MP
204.
1
L
2
L
L
3
button to show
x5
x5
x5

Werbung

loading