Herunterladen Inhalt Inhalt Diese Seite drucken

Normal Operation / Flame Sensor Timing; Fonctionnement Normal/ Temps De Révélation Flamme - Riello Burners RS 250/M Anleitungen Für Einbau, Betrieb Und Wartung

Gebläse - gasbrenner
Inhaltsverzeichnis

Werbung

NORMAL OPERATION / FLAME SENSOR TIMING

The control box has a further function by means of which it is possible to check the correct running of the burner (signal: GREEN LED
permanently lit up).
In order to use this function, it is necessary to wait at least ten seconds from the firing up of the burner and press the button of the control box for
a minimum of three seconds.
Once the button has been released, the GREEN LED will start to flash, as illustrated in the diagram below.
GREEN LED on
wait at least 10 secs
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will identify the SENSOR TIMING o f the probe from opening of the gas valve, according to the table below.
SIGNAL
1 flash
2 flashes
6 flashes
FONCTIONNEMENT NORMAL/ TEMPS DE RÉVÉLATION FLAMME
La boîte de contrôle a une autre fonction qui permet de contrôler si le brûleur fonctionne correctement (signalisation: LED VERT tou-
jours allumé).
Pour utiliser cette fonction, il faut attendre au moins dix secondes après l'allumage du brûleur et appuyer sur le bouton de la boîte pendant au
moins trois secondes.
Après avoir relâché le bouton, le LED VERT se met à clignoter comme indiqué sur la figure suivante.
VOYANT VERT allumé
attendre au moins 10s
Les impulsions du LED constituent un signal espacé d'environ 3 secondes.
Le nombre d'impulsions indique le TEMPS DE RÉVÉLATION de la sonde dès l'ouverture des vannes gaz, comme d'après le tableau
SIGNAL
1 clignotement
2 clignotements
6 clignotements
Press button
for > 3 secs
FLAME SENSOR TIMING
0.4 secs
0.8 secs
2.8 secs
Appuyer sur le bouton
pendant > 3s
TEMPS DE REVELATION FLAMME
0.4 s
0.8 s
2.8 s
Interval
Signal
3 secs
Each time the burner is started up, this information is up-
dated
Once the reading has been taken, by pressing the button
on the control box briefly, the burner repeats the start
cycle.
WARNING
If a timing of > 2 seconds occurs, delayed start-up is
present.
Check the setting of the hydraulic brake in the gas valve
and the setting of the air gate valve and the combustion
head.
Intervalle
signal
Cette donnée est mise à jour à chaque démarrage du
brûleur.
Après avoir procédé à la lecture, il suffit d'appuyer
brièvement sur le bouton de la boîte de contrôle pour que
le brûleur répète le cycle de démarrage.
ATTENTION
L'allumage est retardé si le temps est >2 s. Contrôler le
réglage du frein hydraulique sur la vanne gaz ainsi que le
réglage du volet d'air et de la tête de combustion.
37
Signal
3s
signal
GB
F
suivant..

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

866 t

Inhaltsverzeichnis