Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 65

6 TECHNICAL DATA

Electrical Safety
● Pollution Degree: 2
● Protection (EN 60529): IP20
● Protection Class: (IEC 1140) I
● Overvoltage Category: III
● Bus: SELV DC 24 V
EMC-Compliance
Complies with EN 50081-1 and EN 50082-2, EN 50090-2-2
Environmental
● Operating Temperature: 0°C to +45°C
● Storage Temperature: -25°C to +70°C
● Rel. Humidity (non condensing): 5 % to 93 %
Certification
KNX registered
CE-Signage
According to EMC recommendations (domestic and commercial buildings), low voltage recommendations
Mechanical Data
● Casing: Plastic LEXAN UL-94-V0
● Measurements of casing: Width: 106mm, Height: 55mm, Length: 86mm
● Weight: 200 g
● Mounting: on 35mm DIN rail
Operating Elements
● Programming Button to toggle between normal and addressing mode
● 3 buttons (MOVE, Prg/Set, ESC) on display front to commission the device and set parameters
Display Elements
● Red LED to indicate KNX Normal-/Addressing Mode
● Green PWR-LED to signal device readiness (blinks when in normal operation mode)
● Red ERR-LED to signal fault status
● LC-Display, 2 lines with 12 characters each with menu for commissioning and setting of parameters.
Inputs
● 2 x passive binary input for connection of conventional pushbutton or presence detector 9-32VDC or
8-26VAC, max wire length 15m
DALI-Bus
● Connection of up to 64 ECGs complying to IEC 60926
● DALI-Voltage 18-21VDC, short circuit proof
● It is not allowed to use other control devices (DALI-Master devices) within the same line.
Power Supply
● Power Supply 110 to 240 V, 50 to 60Hz, max. 0,1A
● Additional Power Supply via the EIB Bus
Connectors
● EIB bus connector
● Power Supply: screw connector 3x 1,5mm² single or threaded core
● DALI-Bus: screw connector 2x 1,5mm² single or threaded core
● Binary input: screw connector 2x 1,5mm² single or threaded core
31

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis