ELECTRICAL CONNECTIONS
WARNING: disconnect the network voltage before connecting the device to the
power network!
For electrical connection diagrams, see the following examples.
1. Connect the bus cable's red wire to the terminal's red connector (+) and the black wire to the black con-
nector (-). Up to 4 bus lines (wires of the same colour in the same connector) can be connected to the
bus terminal.
2. Insulate the screen, the electrical continuity conductor and the remaining white and yellow wires of the
bus cable (should a bus cable with 4 conductors be used), which are not needed.
Connection examples
ballast
DALI
After connecting the DALI control wires, the optional external pushbuttons can be connected.
The binary inputs are passive meaning that an auxiliary 8-26VAC or 9-32V DC voltage is required to operate
22
1 Bus device connection
2 Bus cable connection
External
Pushbuttons
ballast
DALI
External
Power supply
8÷26 Vac/9÷32 Vdc