Inverter-kit (drehzahlregler)
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Check motor operation
.
Press Hand (manual operating mode
Press I: the motor starts
Press 0: and check the motor direction of rotation: viewed from
the motor cooling fan side, rotation must be anticlockwise
If this is not the case, alter the connection between motor and In-
verter, as in Fig. 16.
U
V
SED2
W
U
V
SED2
W
D8195
before performing this operation, cut off power
and wait 5 m. so that the EMC filter in the Inverter
time gets discharged
WARNING
Restore power to system: the burner selector must be set to 0
Proceed to Expert Level configuration to set the digital and ana-
logue inputs
.
Set the following parameters:
to 3 (View Expert Level Parameters)
P0003:
In 000 to 52.3 In 001 to 52.3 (generic error)
P0732:
(terminals 24-25 relay output status)
P0748:
with LMV52...
In 000 a 2 In 001 a 2 (0-20mA)
P0756:
see detail A Fig. 15
with REC37...
In 000 a 0 In 001 a 1 (0-10mA)
see detail B Fig. 15
set pos. 6* (default value 4)
P1800:
* See table at page 13.
to 1 (return to Standard Display)
P0003:
Press
until display reads: r0000
Press P: display shows motor present frequency
Press Auto: inverter is ready for automatic operation. Display
reads: "Auto"
6112
First start-up
)
.
U
V
M
W
U
V
M
W
Fig. 16
.
.