Herunterladen Diese Seite drucken
Emerson FSE-0 series Betriebsanleitung
Emerson FSE-0 series Betriebsanleitung

Emerson FSE-0 series Betriebsanleitung

Steuerteil für drehzahlregler
Vorschau ausblenden Andere Handbücher für FSE-0 series:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 2
FSE Control Modules are simple and economical
devices that provide analogue 0...10 V electrical
signals based on condensing pressure changes. They
have been optimized to meet the requirements of air-
cooled condensers. Additional conditioning of the
output signal is not necessary. FSE are the ideal
signal source for EC type fan motors.
!
Safety instructions:
• Read
installation
instructions
Failure to comply may result in device failure,
system damage or personal injury.
• It is intended for use by persons having the
appropriate knowledge and skill.
• Before opening any system make sure pressure
in system is brought to and remains at
atmospheric pressure.
• FSE are factory set to a specific pressure at
which output voltage is 0V (point Z in Fig. 6). If
adjustment is needed, refer to instructions for
proper procedure. Improper adjustment may
result in system damage or failure.
• Do not exceed safe working pressure.
Mounting location:
see Fig. 1: after condenser (1) before accumulator
(2), preferred with pressure connection down. (3) =
EC-type fan motor, (4) = evaporator, (5) = power
supply of EC motor
Pressure connection:
See Fig. 2 for thread connection. Use copper gasket
(1).
See Fig. 3 for solder connection. Use damp cloth (2)
to keep housing temp. below 70°C while soldering.
Electrical connection
Use PS3-Nxx cable assembly (DIN 43650). Push
plug slightly on the pins of control module. Only
one direction possible see Fig. 4. No gasket required.
Fasten screw with 0,05 Nm.
PS3-Nxx cable color code: blue = GND; brown =
10 V; black = signal.
Note: Plug can not be repaired. In case of failure
replace connector.
FSE__65094__R08 .docx
Operating Instructions
Operating Instructions
Control Modules FSE-0
Control Modules FSE
Leakage test:
Leakage test:
• After completion of installation, a test pressure
must be carried out as follows:
-
- According to EN378 for systems which must
comply
with
directive 97/23/EC
- To maximum working pressure of system for other
-
applications
thoroughly.
Warning:
Warning:
1.
1. Failure to do so may result in loss of refrigerant
and person injury.
2. The pressure test must be conducted by skilled
2.
persons with due respect regarding the danger
related to pressure.
Setting
Setting
Minimum pressure for output voltage
Minimum pressure for output voltage 0 (point Z) per
transfer characteristic Fig. 6 is adjustable. FSE-0
transfer characteristic Fig. 6 is adjustable.
Control Modules are factory preset to the pressure
Control Modules are factory preset
values in the table below.
values
Factory Set Point
Factory Set Point
Type
Type
Refrigerant
FSE
FSE-01_ R134a
FSE-02_ R22
FSE
FSE-02_ R407C
FSE
FSE-02_ R507
FSE
FSE-03_ R410A
FSE
For temperatures below these values FSE output
For temperatures below these values FS
signal will be zero
signal will be zero.
For adjustment to other settings follow procedure
For adjustment to other settings follow procedure
below before mounting FSE (Numbers refer to Fig.
below before mounting FSE (Numbers refer to Fig.
5):
5):
Remove sealing cap (3). Insert enclosed 2mm allen
Remove sealing cap
key (2) into adjustment screw (1). Turn allen key
key (2) into adjustment screw (1). Turn allen key
clockwise (+) to increase, or counterclockwise (-) to
clockwise (+) to increase, or counterclockwise (
decrease pressure setting. Do not turn adjustment
decrease pressure setting. Do not turn adjustment
screw
screw more than 3 turns clockwise (+3).
1 turn causes a pressure change of approximately 2.6
1 turn causes a pressure chan
bar.
bar.
Replacement for 07
Replacement for 07
Emerson Climate Technologies GmbH
Holzhauser Str. 180 -
GB
www.emersonclimate.eu
European
pressure
equipment
Pressure bar
Temp. °C
7.0
35
14.5
43
14.5
37.5
14.5
36.5
19.0
35
Date: 05.02.2013
Climate Technologies GmbH
D-13509 Berlin
Germany
Germany
emersonclimate.eu
To readjust to factory setting, a pressure gauge, a
To readjust to factory setting, a pressure gauge, a
constant voltage of 10 VDC and a DC volt meter is
constant voltage of 10 VDC and a DC volt meter is
needed. Apply constant voltage between pin 2 (+)
needed. Apply constant voltage between pin 2 (+)
and pin 4 (-). Connect voltage meter between pin 1
and pin 4 (
(+) and pin 4 (-). Apply pressure of
(+) and pin 4 (
maximum operating pressure PS, than decrease
maximum operating pressure PS, than decrease
pressure slowly to the needed setpoint per table
pressure slowly to the needed setpoint per table
"Factory Set Point". Pressure should not be below
"Factory Set Point". Pressure should not be below
setpoint at any time. Adjust voltage with adjustment
setpoint at any time. Adjust voltage with adjustment
screw (1) to
screw (1) to 0,5 V. For confirmation decrease
pressure to ~30% of maximum pressure PS, than
pressure to ~30% of maximum pressure PS, than
increase to ~60% of PS, than decrease again slowly
increase to ~60% of PS, than decrease again slowly
to setpoint. If necessary correct again with
to setpoint. If necessary correct again with
adjustment screw (1).
adjustment screw (1).
After adjustment insert sealing cap (3) and make
After adjustment insert sealing cap (3) and make
sure that it is properly fitted. IP65 protection
sure that it is properly fitted. I
requires firmly sealed plug.
requires firmly sealed plug.
Technical Data
Technical Data
Supply voltage:
Supply voltage:
Operating current
Operating current
Output signal:
Output signal:
Max. medium temperature at
Max. medium temperature at
pressure connection:
pressure connection:
Ambient temperature range TS:
Ambient temperature range TS:
Max. operating
Pressure PS
FSE-01_:
01_:
27 bar
FSE-02_:
02_:
32 bar
FSE-03_:
03_:
45 bar
Medium
HFC, HCFC
compatibility:
compatibility:
Protection class:
Protection class:
IP 65 according to EN
60529/IEC 529
Marking:
, UL (File Nr. 355325)
~60% of
10 VDC
1 mA
0 ... 10 V
70°C
-20°C ... +65°C
Test Pressure
PT
30 bar
36 bar
48 bar
PCN: 0716136

Werbung

loading

Inhaltszusammenfassung für Emerson FSE-0 series

  • Seite 1 Emerson Climate Technologies GmbH Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Operating Instructions Operating Instructions Germany Germany Control Modules FSE Control Modules FSE-0 www.emersonclimate.eu emersonclimate.eu FSE Control Modules are simple and economical To readjust to factory setting, a pressure gauge, a To readjust to factory setting, a pressure gauge, a devices that provide analogue 0…10 V electrical...
  • Seite 2 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Betriebsanleitung Betriebsanleitung Germany Germany Steuerteil FSE-0 für Drehzahlregler 0 für Drehzahlregler www.emersonclimate.eu www.emersonclimate.eu FSE Steuerteile sind einfache und ökonomische 4). Keine Dichtung erforderlich. Schraube mit max.
  • Seite 3 Emerson Climate Techno Emerson Climate Technologies GmbH Holzhauser Str. 180 Holzhauser Str. 180 - D-13509 Berlin Instructions de service Instructions de service Germany Germany Modules de contrôle FSE Modules de contrôle FSE-0 www.emersonclimate.eu www.emersonclimate.eu Le module FSE est un produit simple et Code couleur du câble PS3...
  • Seite 4 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Instrucciones de funcionamiento Instrucciones de funcionamiento Germany Germany Módulo de Control FSE Módulo de Control FSE-0 www.emersonclimate.eu www.emersonclimate.eu Los módulos FSE son aparatos simples y PS3-Nxx código color cables: azul = Tierra; Marrón Para reajustar nuevamente el módulo al valor...
  • Seite 5 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Istruzioni operative Istruzioni operative Holzhauser Str. 180 - D-13509 Berlin Modulo di Controllo FSE Modulo di Controllo FSE-0 Germany Germany www.emersonclimate.eu www.emersonclimate.eu un voltmetro DC. Applicare un voltaggio costante un voltmetro DC. Applicare un voltaggio costante Il Modulo di Controllo FSE è...
  • Seite 6 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Instrukties voor het gebruik Instrukties voor het gebruik Holzhauser Str. 180 - D-13509 Berlin Regel module Ventilator toerenregelaar Regel module Ventilator toerenregelaar Germany Germany FSE- www.emersonclimate.eu www.emersonclimate.eu regel module eenvoudige Gebruik kabel FSE Gebruik kabel FSE-Nxx (Din 43650).
  • Seite 7 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Návod k montáži Návod k montáži Germany Germany Silový modul Silový modul FSE-0 www.emersonclimate.eu www.emersonclimate.eu Řídící modul FSE je jednoduché a ekonomické vyjmout krycí zátku (3) vyjmout krycí...
  • Seite 8 Emerson Climate Technologies Emerson Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Instrukcja obsługi Instrukcja obsługi Germany Germany Moduły steruj ą Moduły steruj ą ce FSE-0 www.emersonclimate.eu www.emersonclimate.eu Moduły sterujące FSE, są prostymi PS3-Nxx kod kolorów kabli: niebieski = GND;...
  • Seite 9 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Instruc iuni de utilizare iuni de utilizare Germany Germany Module de Control FSE de Control FSE-0 www.emersonclima www.emersonclimate.eu Modulele de Control FSE sunt produse simple şi Nota: Mufa Nota: Mufa nu se poate repara.
  • Seite 10 Emerson Climate Technologies GmbH Technologies GmbH Holzhauser Str. 180 - D-13509 Berlin Germany Germany FSE-0 www.emersonclimate.eu www.emersonclimate.eu 0,05 0…10 PS3-Nxx =GND (« »; =10 ; (+3). . FSE • • 2 (+) 4 (-). EN378 • 1 (+) 4 (- ~60% 97/23/EC;...
  • Seite 11 Emerson Climate Technologies GmbH Emerson Climate Technologies GmbH Holzhauser Str. 180 - D- -13509 Berlin FSE- Germany www.emersonclimate.eu www.emersonclimate.eu max. 70°C < 15 Nm < 15 Nm Fig.1 Fig. 2 Fig. 3 Speed Fig. 4 Fig. 5 Fig. 6 adjustable...

Diese Anleitung auch für:

Fse-01Fse-02Fse-03