PROBLEM
5. Device does not
regenerate.
6. Brine is not totally or
partially drawn during
the regeneration stage.
7. The salt tank is not
sufficiently loaded or
not at all with water.
8. Excessive salt
consumption during
regeneration.
9. The salt tank is load-
ed with more water than
needed.
10. Water has a salty
taste.
11. Water permanently
flows through dis-
charge.
12. Lack of information
on display.
13. The message
[System maintenance]
appears on display.
38
CAUSE
1. Power supply stopped.
2. Salt in insufficient quantity in the
tank.
3. Brine is not partially or totally
drawn during the regeneration
stage.
4. The control valve is defective or
the settings were changed.
5. The salt tank was not supplied
with water or is insufficiently sup-
plied with water.
1. Low pressure in the water supply
installation.
2. Blocked/clogged brine injector
or tube.
3. Air/aeration valve blocked with
salt crystals.
4. High pressure loss (blocked
control valve, filtering agent or
distributors).
5. The brine line is not tight, and air
is also injected as such.
6. Settings were modified.
1. Low supply water pressure.
2. Clogged brine injector or tube.
3. Blocked aeration device.
4. Settings were modified.
5. Float remained blocked.
1. Settings were changed.
2. The salt tank is loaded with more
water than needed.
1. Pressure of supply water too
high.
2. Settings were modified.
1. The filtering agent was not suffi-
ciently rinsed.
2. Low output during washing.
1. The power supply was cut during
regeneration.
2. The packing of the distance meter
assembly is damaged.
1. Voltage absence.
2. Defective transformer.
3. Defective electronic plate.
1. Soft error
SOLVING
1. Check the power supply.
2. Check the salt level and fill the
salt tank.
3. See paragraph 6.
4. Check the control valve and
settings.
5. See paragraph 7.
1. Check the supply pressure.
2. Clean the brine injector and/or
tube.
3. Clean the air/aeration valve.
4. See paragraph 1.4.
5. Check packing.
6. Contact the producer.
1. Check the network pressure.
2. Clean the brine injector or tube.
3. Check and clean the aeration
device.
4. Contact the producer.
5. Draw the float (upwards) on the
rod.
1. Contact the producer.
2. See paragraph 9.
1. Check the supply pressure.
2. Contact the producer.
1. Increase the operation time
[Rinse]
2. Check and clean DLFC.
1. Put the valve on by-pass up to the
power supply.
2. Check and replace the damaged
packing.
1. Check the power supply both of
the electric network and the valve.
2. Replace the transformer.
3. Replace the electronic plate.
1. Restart the voltage supply.

Werbung