Herunterladen Inhalt Inhalt Diese Seite drucken

Galletti LED 503 Bedienungsanleitung Seite 16

Steuerung für endgeräte
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 34
LED 503
FORESEEN CONFIGURATIONS (PARAMETER P00)
009
> System pipes
: 2
> Valve
: no
> Electrical heater
: yes
> Speed
: 3
G B
> Summer/winter switching logic: air
010
> System pipes
: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: local
011
> System pipes: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: remote
012
> System pipes
: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: water
013
> System pipes
: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: local
014
> System pipes
: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: remote
015
> System pipes
: 2
> Valve
: 2/3 way
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: water
016
> System pipes
: 2
> Valve
: 3 way
> Electrical heater
: yes
> Speed
: 3
> Summer/winter switching logic: local
FC66002953 - rev. 02
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
017
> System pipes
: 2
> Valve
: 3 way
> Electrical heater
: yes
> Speed
: 3
> Summer/winter switching logic: remote
018
> System pipes
: 2
> Valve
: 3 way
> Electrical heater
: yes
> Speed
: 3
> Summer/winter switching logic: air
019
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: local
020
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: remote
021
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 3
> Summer/winter switching logic: air
022
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: local
023
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: remote
024
> System pipes
: 4
> Valve
: no
> Electrical heater
: no
> Speed
: 4
> Summer/winter switching logic: air
16

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading