2 Terminal block
Low voltage controls: The maximum current which may be
switched per output is 2A with cos
establishing current below 16A).
If the load exceeds either of these values, the control must
be relayed using a contactor that must not be installed in
the Diematic 3 control panel under any circumstances.
24/03/06 - 8666-4562A
(1) If using a two-way motor
ϕ
= 0.7 (= 450W
Connect open to terminal
terminal N.
If using a thermal motor
Connect between terminal
(2) Safety thermostat
If using underfloor heating, it is imperative that a temperature limit of
50°C is installed and a safety thermostat set to 65°C (cf. NF P 52-
303-1) is fitted, which interrupts the operation of the heating pump in
the circuit concerned should overheating occur.
Connect the safety thermostat wires to the 5 pin connector at the
point marked TS terminals (2) after removing the jumper from
terminals (2).
The original factory setting of the boilers limits the temperature in the
primary circuit to 50 °C.
AD 202
, close to terminal
and neutral to
(open) and terminal N.
7