Herunterladen Inhalt Inhalt Diese Seite drucken

Parker P4CG4465 serie Einbau Und Einstellanleitung Seite 7

Lucifer epp4 druckregler
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

'CALYS' OPTION
This option should be used outside ATEX area.
Order No.:
496449 (Communication cable)
'Calys'
is a software to set all parameters of the EPP4 Comfort.
The software is free of charge but you have to buy the specific
cable 496449 to establish the communication with the EPP4.
'Calys'
has 3 levels of use, with 2 different passwords:
View
view only, no settings possible, no password
-
-
Setting
for basic settings and maintenance
Factory
only for authorized people, all settings
-
Parameters must be changed within the functional limits of the pressure regulators.
To use software Calys, you have to order specific communication cable ref 496449, then:
You can download free Calys software from www.parker.com/fcde/support
-
-
Install the software and use the Help File (pdf), it is the "?" on the page, up right corner. Select first your
language (E, F, D, I), the Help File will be in the same language.
-
Password needed to access "setting" level is "glage"
-
Connect the EPP4 to your computer (see below)
-
Re-set the EPP4 to your needs
Connection
Use the specific cable 496449 to connect the EPP4 to your computer:
RS-232
-
M12 connector on EPP B connector
-
Sub-D on computer
-
Select the Port Com in the TOOL menu
-
The "LED" bottom right corner becomes green if
communication is ok
USB
Install the driver from the CD delivered with the USB kit.
Read carefully the manual of the USB kit.
-
M12 connector on EPP B connector
-
Sub-D on USB adapter
-
USB adapter on computer
-
Select the Port Com in the TOOL menu
Bulletin 408283 R02 13.06.2013 - Part Nr. 497057
- 7/24 -
EPP4 Pressure Regulator

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

P4cg6161 serieP4cg9161 serie

Inhaltsverzeichnis