1018 Tuning ON/OFF
0=Tuning off
1=Tuning on
1019 Automatic/Manual selection
0=automatic ; 1=manual
1020 OFF LINE
1100 Process with decimal point
1101 Setpoint 1 with decimal point
1102 Setpoint 2 with decimal point
1103 Setpoint 3 with decimal point
1104 Setpoint 4 with decimal point
1105 Alarm 1 with decimal point
1106 Alarm 2 with decimal point
1107 Alarm 3 with decimal point
1108 Setpoint gradient with decimal point
1109 Percentage heating output (0-1000)
1110 Percentage heating output (0-100)
1111 Percentage cooling output (0-1000)
1112 Percentage cooling output (0-100)
2001 Parameter 1
....
....
2085 Parameter 85
4001 Parameter 1
....
....
4085 Parameter 85
3
If it is 0, control is desabled. If it is different from 0, it is "maximum time that can elapse
between two pollings before the controller goes off-line"
If it goes Off-line, the controller goes to Stop mode, the control output is desabled, but the
controllers keeps alarms activated.
4
Parameters changed using serial address from 4001 to 4085 are saved in eeprom only after
10'' after the last writing of parameters.
26
3
time (milliseconds)
4
R/W
0
R/W
0
R/W
0
RO
?
RW
EEPROM
RW
EEPROM
RW
EEPROM
RW
EEPROM
RW
EEPROM
RW
EEPROM
RW
EEPROM
RO
EEPROM
RW
0
RW
0
RO
0
RO
0
R/W
EEPROM
R/W
EEPROM
R/W
EEPROM
R/W
EEPROM
R/W
EEPROM
R/W
EEPROM