19. ∆T for cooling ON
Set temp difference between out temp & return temp of circulating water of
Cooling operation.
When temp gap is enlarged, it is energy saving but less comfort. When the
gap gets smaller, energy saving effect gets worse but it is more comfortable.
Setting range is 1°C ~ 15°C
Auto
20. Outdoor temp. for (Heat to Cool)
Set outdoor temp that switches from heating to cooling by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
21. Outdoor temp. for (Cool to Heat)
Set outdoor temp that switches from Cooling to Heating by Auto setting.
Setting range is 5°C ~ 25°C
Timing of judgement is every 1 hour
Tank
22. Floor operation time (max)
Set max operating hours of heating.
When max operation time is shortened, it can boil the tank more frequently.
It is a function for Heating + Tank operation.
23. Tank heat up time (max)
Set max boiling hours of tank.
When max boiling hours are shortened, it immediately returns to Heating
operation, but it may not fully boil the tank.
24. Tank re-heat temp.
Set temp to perform reboil of tank water.
(When boiled by heat pump only, (51°C – Tank re-heat temp) shall become
max temp.)
Setting range is -12°C ~ -2°C
26
Initial setting: 5°C
Initial setting: 15°C
Initial setting: 10°C
Initial setting: 8h
Initial setting: 60min
Initial setting: -
8°C
Out
Return
Return — Out = 1°C ~ 15°C
Heat
Outdoor temp. rising
Cool
15°C
Heat
Outdoor temp. dropping
Cool
10°C
Heat
30min ~ 10h
Heat
5min ~ 4h
-12°C ~ -2°C
Tank
Tank