Floor heating + Swimming pool
Outdoor
Connect radiator and swimming pool to 2 circuits through Tank Unit as shown in fi gure.
Install additional pool heat exchanger, pool pump and pool sensor on pool circuit.
Remove remote controller from Tank Unit and install in room where fl oor heating is installed.
Circulation water temperature of fl oor heating and swimming pool can be set independently.
 Must connect swimming pool to "Zone 2".
If it is connected to swimming pool, operation of pool will stop when "Cooling" is operated.
(NOTE)
Zone 1 should always set with higher water temperature than zone 2. If not set correctly, water temperature fl ow into zone 1 water circuit
may higher than the set temperature.
Please adjust fl ow rate of zone 1 and zone 2 to be in balance. If it is not adjusted correctly, it may affects the performance.
(If zone 2 pump fl ow rate is too high, there is possibility that no hot water fl owing to zone 1.)
Flow rate can be confi rmed by "Actuator Check" from maintenance menu.
2 How to fi x cable
Connecting with external device (optional)
All connections shall follow to the local national wiring standard.
It is strongly recommended to use manufacturer-recommended
parts and accessories for installation.
For connection to main PCB 4
1. Two-way valve shall be spring and electronic type, refer to "Field
Supply Accessories" table for details. Valve cable shall be (3 x
2
min 1.5 mm
), of type designation 60245 IEC 57 or heavier, or
similarly double insulation sheathed cable.
* note: - Two-way Valve shall be CE marking compliance
component.
- Maximum load for the valve is 9.8VA.
2. Room thermostat cable must be (4 or 3 x min 0.5 mm
designation 60245 IEC 57 or heavier cord, or similarly double
insulation sheathed cable.
3. Extra pump cable shall be (2 x min 1.5 mm²), of type designation
60245 IEC 57 or heavier.
4. External control shall be connected to 1-pole switch with min
3.0 mm contact gap. Its cable must be (2 x min 0.5 mm
insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
5. Room sensor zone 1 cable shall be (2 x min 0.3 mm²) double
insulation layer of PVC-sheathed or rubber-sheathed.
6. Outdoor air sensor cable shall be (2 x min 0.3 mm²) double
insulation layer of PVC-sheathed or rubber-sheathed.
Optional cables:
2-way valve cable
Room thermostat zone 1 cable
Extra pump cable
14
Indoor
Heat EXT
Radiator (zone 1)
Optional cables:
External control
cable
Room sensor
zone 1
Outdoor air sensor
cable
Remote controller
cable
Power Supply 1 cord
Power Supply 2 cord
Indoor/Outdoor Connecting cable
Pool Pump
Pool Sensor
Swimming pool
For connection to Optional PCB 5
1. Pool pump cable shall be (2 x min 1.5 mm²), of type designation
60245 IEC 57 or heavier.
2. Room thermostat zone 1 and zone 2 cable shall be (4 x min
0.5 mm²), of type designation 60245 IEC 57 or heavier.
3. Room sensor zone 1 and zone 2 cable shall be (2 x min 0.3 mm²),
double insulation layer (with insulation strength of minimum 30V)
of PVC-sheathed or rubber-sheathed cable.
4. Pool water sensor cable shall be (2 x min 0.3 mm²), double
insulation layer (with insulation strength of minimum 30V) of PVC-
sheathed or rubber-sheathed cable.
2
), of type
5. Demand signal cable shall be (2 x min 0.3 mm²), double insulation
layer of PVC-sheathed or rubber-sheathed cable.
6. SG signal cable shall be (3 x min 0.3 mm²), double insulation layer
of PVC-sheathed or rubber-sheathed cable.
7. Heat/Cool switch cable shall be (2 x min 0.3 mm²), double insulation
2
layer of PVC-sheathed or rubber-sheathed cable.
), double
8. External compressor switch cable shall be (2 x min 0.3 mm²),
double insulation layer of PVC-sheathed or rubber-sheathed cable.
.
rms
Setting of remote controller
Installer setting
System setup
Optional PCB connectivity - Yes
Zone and Sensor - 2 Zone system
Zone 1:Sensor
Room thermostat
Internal
Zone 2
Swimming pool
T