• Water quality:
- In order for the heat pump to operate under good conditions and provide optimum performance, it is essential to
ensure that the system's water circuit is clean. If the water circuit becomes clogged, this will significantly affect the
machine's performance. The circuit must therefore be cleaned with suitable products in compliance with current
standards as soon as it is installed, both for new and renovation work.
We recommend the use of products which are compatible with all metals and synthetic materials and approved by
official bodies.
Recommendations regarding water quality:
- PH: 6 to 9.
GB
- TH: 10 to 20°F.
- Dry material in suspension: < 2 g/l
- Granulometry: < 0.4 mm
- Chloride: 50 mg/l maximum
- Conductivity: 50 to 500 µS/cm2
- Resistivity: 1 to 10 kΩ
- Fibre: no fibres.
Any disorder which may occur on our machines due to the poor quality of the fluid in the installation will not be
covered by the warranty.

6.1.3 - ELECTRICAL SYSTEM

• The power cables are well fixed to their connection terminals. Terminals that are poorly tightened may cause overheating
and malfunctions.
• The electric cables are well insulated from any sections of sheet metal or metal parts which could damage them.
• The probe, control and power cables are properly separated.
• The machine is earthed.
6.1.4 - MISCELLANEOUS
• Overall good condition of the apparatus.
• No tools or other foreign objects inside the apparatus.
6.2 - CONFIGURATION AND PARAMETERISATION
6.2.1 - AUTO-ADDRESSING OF INDOOR AND OUTDOOR UNITS
• Set the control unit selector to "OFF".
• Turn on the indoor and outdoor units. The unit cycles through an automatic addressing phase when the power is first
turned on. This phase may take 2 to 3 minutes and is indicated by the alternate blinking of LED1 and LED2 on the
outdoor unit card.
When these indicator lights cease blinking, addressing is completed and communication between the indoor and outdoor
unit is established.
Note 1:
The addressing phase is indicated on the screen of the RCS-TM80BG keyboard/display unit (if installed) by the flashing
"SETTING" message.
Note 2:
Should a problem arise during this automatic addressing phase, a new phase can be restarted. To do this, simply
disconnect the power supply for at least 1 minute and when power is restored, press the black "AUTO ADD" button on
the outdoor unit's electronic board.
Meaning of LED1 and LED2 activity on the outdoor unit's board.
= ON steady
= ON blinking
= OFF
Meaning
Auto-addressing in progress
Power ON:
Step 1:
no communication
Step 2:
communication received from
the indoor unit
Step 3:
normal communication
Alarm message
No charge indicator
Refrigerant recovery mode
Alarms
(Refer to the details in the outdoor unit's
maintenance and troubleshooting
manual)
14
LED1 LED2
Alternating blinking
Simultaneous blinking
Repeated and alternating
blinking (of each indicator
light)