Electrical installation

Important notes

6
Electrical installation
Important notes
(
Stop!
Possible overheating of the brake resistor during operation
Inadequate heat dissipation during operation can cause the brake resistor to
overheat.
Possible consequences:
The brake resistor is destroyed.
ƒ
The drive is not braked but coasts to a standstill.
ƒ
Protective measures:
Always connect the thermal contact of the brake resistor.
ƒ
Integrate the thermal contact into the overall equipment monitoring
ƒ
apparatus in such a way that the supply of power to the standard device is
switched off if the brake resistor overheats (e.g. switch−off by means of
mains contactor control).

Connection data

RB1, RB2
(brake resistor)
PE
(PE conductor)
T1, T2
(thermal contact)
50
Cable gland
connection
Screw terminal
M25
M12
Screw terminal
l
Type of
Size of connection Tightening torque
0.5 ... 10 mm
20 ... 6 AWG
Screw
0.25 ... 4 mm
24 ... 12 AWG
2
1.5 ... 1.8 Nm
13.3 ... 15.9 lb−in
2.2 ... 2.7 Nm
M4
19.5 ... 23.9 lb−in
2
0.6 ... 0.8 Nm
5.3 ... 7.1 lb−in
EDKRBS047R DE/EN/FR/ES/IT 9.0